RS-Sensor Termination Detail
The RS Sensor is remotely mounted and installed (up to 500ft) in the zone it is recommended to
use shielded cable (20AWG conductors) if installing RS-sensor only.
If BACview is installed remotely using the same cable is recommended to use shielded cable
(18AWG conductors).
Room
Sensor
DDC - Unit
Field installed wiring
four conductor shielded
cable
Rnet port termination:
Black = Ground
White = R-net +
Blue = R-net -
Red =12VDC