1. Appearance
1. WARNING
Please install the unit in compliance with local CODES, regulations and standards;
Please use a solid base, such as 2 pieces of 16” x 16” x 4” concrete blocks or an equipment
base of 16” x 32 inches minimum size.
Confirm power voltage and frequency; 208-240 volts, 60 Hz. 20 Amps.
2 Hot Leads, 1 Ground. No Neutral, Non GFCI. Within 50 feet of the breaker box, use 12 AWG
gauge wire ( 12-2+ Ground), 50-150 feet distance from breaker box to the heater, pls use 10
AWG wire ( 10-2+Ground).
The heater must be BONDED to a ground rod, using #8 AWG bare copper wire.
An external timer or a service disconnect must be installed in accordance with local electric
codes.
1 1/2” schedule 40 pvc must be used to connect plumbing.
WATER AND ELECTRICITY DONT MIX. PLEASE USE ALL PRECAUTIONS AND DO NOT
SHORT CUT ANY SAFETY PROCEDURES.
Do not install this heater in an enclosed room. Without adequate air supply, the heater will not
function well. If the unit was installed in a closed area or limited space, please consider the size
of room and ventilation to prevent suffocation caused by refrigerant leakage.
Be sure to Install a BONDING wire to a ground rod, using #8 AWG Bare Copper Wire
Fibropool FH 270 is weatherproof and designed to be outdoors. But is is not designed to be
below eaves of the roof, where water pours onto it. Please use common sense in choosing a
location.
Do NOT install this heater where there may be flammable gas.
This heater is made of mostly metal alloys, and may have sharp edges, please use gloves while
handling it.
Heater weighs about 150 lbs. It is a 2 person handling size and weight.
V-2105 Fibropool Co LLC, Ms USA