EasyManua.ls Logo

Field Controls CK-61 - Installation; Mounting Junction Box; Oil Fired Secondary Safety Switch (WMO-1); Mounting in the Vent Pipe

Field Controls CK-61
8 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
page 2
PRESSURE SWITCH SENSING TUBE INSTALLATION
1. Attach the
1
4" tubing connector to the pressure tube on the SWG Venter.
(See Figure 3)
2. Connect the supplied
1
4" aluminum tubing to the tubing
connector. Route the tubing to the CK- 61 junction box and
connect the tubing to the pressure switch. When routing the
tubing, avoid kinking the tubing by bending the tubing
too sharply.
3. For remote mounted CK-61 junction box, use a
1
4" OD
copper, aluminum or plastic tubing and route the tubing to
avoid contact with any heat source.
Refer to the SWG Venter installation instructions for setting
system air ow.
SEE THE APPLIANCE MANUFACTURER’S INSTRUCTIONS FOR THE SPECIFIC LOCATION.
IF THE APPLIANCE MANUFACTURER DOES NOT SPECIFY A LOCATION, REFER TO FIGURE 5.
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
INSTALLATION
MOUNTING JUNCTION BOX
The junction box can be mounted at the venter or remotely mounted away
from the venter. (See Figure 1 & Figure 2)
1. Remove one of the knockouts from the side of the junction box where
the pressure switch is mounted. Install the  exible conduit connector
onto the CK-61 junction box and secure with fastening nut. If remote
mounting the CK-61 junction box, mount the  exible conduit connector
onto a 2” x 4” installer supplied junction box.
2. Fasten the  exible conduit from the SWG Venter into the conduit
connector. Mount the CK-61 junction box or installer supplied junction
box onto the wall or  oor joist without straining the  exible conduit.
Fasten the CK- 61 junction box through the four dimpled locations on
the base of the box. (See Figure 3)
OIL FIRED SECONDARY SAFETY SWITCH (WMO-1)
Installation of a SECONDARY SAFETY SWITCH (WMO-1) is recommended
for detecting  ue gas spillage from a blocked  ue system and/or
inadequate draft.
MOUNTING IN THE VENT PIPE
1. Drill or pierce a clean hole (about
3
4” diameter) in the vent pipe near
the appliance outlet. (See Figure 5)
2. The heat transfer tube must have the  ber gasket installed against the
mounting plate before attaching the unit to the vent pipe.
3. Insert the heat transfer tube with gasket into the
3
4” diameter hole
placed in the vent pipe during step 1.
4. Secure the assembly to the vent pipe with a minimum of 4 sheet
metal screws. The channel must be mounted horizontally, unless
speci ed di erently by the appliance manufacturer. (See Figure 5)
CAUTION: Disconnect electrical power supply to the appliance when wiring the
blocked vent switch.
WARNING: Switch connection channel must be mounted horizontally,
unless speci ed di erently by the appliance manufacturer.

Related product manuals