EasyManua.ls Logo

Fike 63-1052 - User Manual

Fike 63-1052
2 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
1 I56-2475-010
3/25/2020
63-1052, 63-1053, and 63-1057
Intelligent Photoelectric Smoke Detectors
INSTALLATION AND MAINTENANCE INSTRUCTIONS
BEFORE INSTALLING
This detector must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Detectors offer maximum performance
when installed in compliance with the National Fire Protection Association
(NFPA); see NFPA 72.
GENERAL DESCRIPTION
Models 63-1052, 63-1053 and 63-1057 are intelligent photoelectric, spot-
type smoke detectors utilizing sensing chambers that are designed to re-
spond rapidly to a broad range of fires. The sensing chamber employs
features that minimize the effects of settled dust on performance. Model
63-1053 uses a thermistor based, 135°F heat detection circuit in addition to the
photoelectric sensing chamber. The 63-1053 also transmits an alarm signal due
to heat (135°F fixed) per UL 521. 63-1057 is designed for use inside the DN-
RECL duct housing only. 63-1057 should not be used in open area applications.
The detector is designed with tri-color LEDs to indicate detector status. The
detector can be programmed to make the LEDs blink or be steady green, am-
ber or red. The detector remote output can be configured to follow the LED
or be independently controlled. A remote LED annunciator is available as an
accessory (RA400Z/RA100Z).
The 63-1052, 63-1053 and 63-1057 require compatible addressable commu-
nications to function properly. Connect these detectors to listed-compatible
control panels only.
SPACING
System Sensor recommends spacing detectors in compliance with NFPA 72. In
low air flow applications with smooth ceilings, the detectors should be spaced
30 feet apart. For specific information regarding detector spacing, placement,
and special applications, refer to NFPA 72 or the System Smoke Detector Appli-
cation Guide, available from Fike. When using the 63-1053 as a heat detector
in FM3210 compliant applications, space detectors 20 feet apart.
Duct Applications: 63-1052 and 63-1053 are listed for use in ducts. See Duct
Applications Guide HVAG53 (formerly A05-1004) for details on pendant
mount applications.
Note: 63-1057 is listed for use inside DNRECL duct smoke detectors.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction (AHJ). Proper wire gauges should be used. The installation wires
should be color-coded to limit wiring mistakes and simplify system trouble-
shooting. Improper connections will prevent a system from responding prop-
erly in the event of a fire.
1. Wire the detector base (supplied separately) per the wiring diagram, Figure 1.
2. Install the detector into the base. Push the detector into the base while
turning it clockwise to secure it in place.
3. Set the desired address using the IR configuration tool (model no. EA–CT).
NOTE: Maximum range for the EA–CT is 30 ft. (9 m).
4. Test the detector(s) as described in the TESTING section of this manual.
SPECIFICATIONS
Normal Operating Voltage: 15 to 30 VDC
Standby Current: 481µA max. @ 24 VDC (continuous broadcasts)
Alarm Current: 2 mA max. @ 24 VDC (LEDs on)
Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Temperature Range: 32°F to 120°F (0°C to 49°C ); 63-1052 and 63-1057; 32°F to 100°F (0°C to 38°C); 63-1053
Heat Detector: 135°F Fixed Temperature Electronic Thermistor
Height: 2.1˝ (51 mm) installed in EBFI or EBI Base
Diameter: 6.1˝ (155 mm) installed in EBFI Base; 4.1˝ (104 mm) installed in EBI Base
Weight: 5.2 oz. (147 g)
FIGURE 1. WIRING DIAGRAM
+
+
LISTED COMPATIBLE
CONTROL PANEL
OPTIONAL RETURN LOOP
+
1
2
3
4
1
2
3
4
CAUTION: DO NOT LOOP
WIRE UNDER TERMINAL
1, 2 OR 3. BREAK WIRE
RUN TO PROVIDE
SUPERVISION OF
CONNECTIONS.
OPTIONAL
REMOTE
ANNUNCIATOR
C0113-01
NOTE: 63-1057 requires a 5-volt zener diode only when connected to an
RA400Z or RA100Z remote LED annunciator.
CAUTION
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the detectors can sense smoke.
Remove detectors prior to heavy remodeling or construction.
TAMPER-RESISTANCE
Models 63-1052 and 63-1053 include a tamper-resistant capability that pre-
vents their removal from the base without the use of a tool. Refer to the base
manual for details on making use of this capability.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All detectors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Detectors
offer maximum performance when tested and maintained in compliance with
NFPA 72.
The detector can be tested in the following ways:
A. Functional
This detector can be functionally tested by using the EA–CT. Follow-
ing the instructions, initiate the detector test sequence. The detector will
then send a test alarm message to the panel. Refer to the control panel
technical documentation for further information.
B. Smoke Entry
The GEMINI model 501 aerosol generator can be used for smoke entry
testing. Set the generator to represent 4%/ft to 5%/ft obscuration as de-
scribed in the GEMINI 501 manual. Using the bowl shaped applicator,
apply aerosol until the panel alarms.
I56-2475-010
704 S. 10th Street
Blue Springs, MO 64015
Phone: 816.229.3405; Fax: 816.228.9277
www.fike.com
R
Question and Answer IconNeed help?

Do you have a question about the Fike 63-1052 and is the answer not in the manual?

Summary

Specifications

Before Installing

General Description

Spacing

Wiring Guide

Tamper Resistance

Testing

Functional Testing

Test detector functionality using the EA-CT tool. Initiates test sequence for panel alarm message.

Smoke Entry Testing

Use GEMINI 501 aerosol generator for smoke entry test. Apply aerosol until panel alarms.

Cleaning

Special Application Mode

FCC Statement

Device and System Security

Overview

The Fike 63-1052, 63-1053, and 63-1057 are intelligent photoelectric smoke detectors designed for rapid response to a broad range of fires. These devices utilize sensing chambers engineered to minimize the impact of settled dust on their performance.

Function Description

These detectors are intelligent, spot-type photoelectric smoke detectors. The 63-1053 model includes an additional thermistor-based, 135°F fixed temperature heat detection circuit, allowing it to transmit an alarm signal due to heat in accordance with UL 521. The 63-1057 model is specifically designed for use within the DNRECL duct housing and is not intended for open area applications.

The detectors feature tri-color LEDs to indicate their status. These LEDs can be programmed to blink or remain steady in green, amber, or red, providing visual cues about the detector's operational state. A remote output is also available, which can be configured to either follow the LED status or be controlled independently. For enhanced visibility, a remote LED annunciator (RA400Z/RA100Z) can be connected as an accessory.

These detectors require compatible addressable communications to function correctly and must be connected to listed-compatible control panels. When configured at the fire alarm control panel, the detector can operate in a special application mode, offering higher sensitivity than typically allowed by UL 268. This mode is suitable for areas where early warning is critical, such as hospitals, museums, and assisted living facilities, provided there are no airborne particulates or aerosols. However, in this special application mode, the detector does not comply with the Cooking Nuisance Smoke Test and is not suitable for areas where cooking appliances or other sources of airborne particulates (e.g., sawing, drilling, grinding operations, textile or agricultural processing, or unvented engines) may be present. For general use or areas with cooking appliances, a normal application detector or normal application mode must be used.

Usage Features

Installation of these detectors must adhere to the control panel system installation manual, the requirements of the Authority Having Jurisdiction (AHJ), and NFPA 72 standards for maximum performance. The detectors are designed to be installed in a base (supplied separately) by pushing and turning clockwise to secure them. The desired address for each detector is set using an IR configuration tool (model no. EA-CT) with a maximum range of 30 feet (9 meters).

For spacing, System Sensor recommends following NFPA 72 guidelines. In low airflow applications with smooth ceilings, detectors should be spaced 30 feet apart. When the 63-1053 is used as a heat detector in FM3210 compliant applications, the spacing should be 20 feet apart. The 63-1052 and 63-1053 models are also listed for use in ducts, with specific guidance available in the Duct Applications Guide HVAG53.

The detectors include a tamper-resistant capability to prevent unauthorized removal from the base without a tool. This feature enhances security and helps maintain system integrity.

Testing of the detectors is crucial after installation and periodically thereafter, in accordance with the AHJ and NFPA 72. Functional testing can be performed using the EA-CT tool, which initiates a test alarm message to the control panel. Smoke entry testing can be conducted using a GEMINI model 501 aerosol generator, applying aerosol until the panel alarms. Alternatively, canned aerosol simulated smoke products (e.g., Home Safeguard Industries 25S, SDi CHEK02, CHEK06, SOLOA4, SMOKESABRE-01) can be used, following manufacturer instructions to avoid misuse or overuse, which may have long-term adverse effects. For the 63-1053 model, direct heat testing can be performed on the thermistors using a hair dryer, heat gun, or dedicated test apparatus, ensuring both thermistors are tested individually and allowing sufficient time for cooling before reset.

Maintenance Features

Before any maintenance, the proper authorities must be notified, and the system or relevant zone disabled to prevent unwanted alarms. Dust covers, provided for limited protection during shipping, must be removed before the detectors can sense smoke and prior to heavy remodeling or construction.

Cleaning involves removing the detector from the system and then carefully vacuuming the screen without removing it. If further cleaning is needed, the chamber cover/screen assembly can be pulled straight out. A vacuum cleaner or clean compressed air can then be used to remove dust and debris from the sensing chamber. After cleaning, the chamber cover/screen assembly is reinstalled by sliding it over the sensing chamber and turning it firmly into place. The main cover is replaced by aligning the LEDs and gently pushing until it locks, ensuring that the thermistors on 63-1053 models are not bent. After reinstallation, the detector must be tested as described in the TESTING section, and disabled circuits reconnected. Finally, the proper authorities must be notified that the system is back online.

Proper wire gauges and color-coded wiring should be used during installation to minimize mistakes and simplify troubleshooting. Improper connections can prevent the system from responding correctly in a fire event.

Fike 63-1052 Specifications

General IconGeneral
Model Number63-1052
Operating Temperature0°C to 38°C
Humidity Range10% to 90% (non-condensing)
Sound Level85dB at 10 feet
ComplianceUL 217, NFPA 72