Technical data Modbus
Bus system Modbus, RTU according to IDA specification
Transmission rate
The transmission Baud rate is automatically detected
Transmission mode Even parity: 8 data bits, 1 stop bit
Odd parity: 8 data bits, 1 stop bit
No parity: 8 data bits, 2 stop bits
The transmission mode is automatically detected
Bus length (max.) 1200 m (without repeater)
Response time: Write: up to 60 ms
Read: up to 60 ms
The communication is ready 30 s after the power on
The use of energy meter in bus with intensive communication could reduce the performance of the bus
Refresh time for the data is 5 s. For this reason one energy meter should be not polled faster as 5 s
247
devices could be connected to the Modbus. With more than 128 devices, a repeater should be used
The interface don’t have a terminal resistor, this must be provided external
For a description of the used registers please look at the register page
Data transmission
Only «Read Holding Registers [03]/ Write Multiple Registers [16]» instructions are recognized.
Up to 20 Registers can be read at a time.
The device supports broadcast messages.
In accordance with the Modbus protocol, a register R is numbered as R - 1 when transmitted.
The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM (transmission
rate, etc.)
Exception Responses
ILLEGAL FUNCTION [01]: The function code is not supported.
ILLEGAL DATA ADDRESS [02]: The address of some requested registers is out of range
or more than 20 registers have been requested.
ILLEGAL DATA VALUE [03]: The value in the data field is invalid for the referenced register.
Changing the Modbus address direct on device
In the menu, go for «U»
Push long ( 3 sec) «Adr»
Push short address +1, push long address +10
Once the desired address is selected wait, to validate, till the root menu to come back