BG-12 Manual Pull Station
Patented, U.S. Patent No. Des. 428,351; 6,380,846; 6,314,772; Other Patents Pending
Document 50964-1 I56-2263-003
Description
The BG-12 pull station is a non-coded, dual-action manual pull station with a hex-lock reset
feature. It provides Fire•Lite control panels with one normally open (N/O) alarm initiating
input. The BG-12 meets the ADAAG controls and operating mechanisms guidelines (sec-
tion 4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate the pull
station. Operating instructions are molded into the pull station handle along with Braille
text. Molded Terminal numbers are also present.
Ratings
Switch contact (N/O) is gold plated for reliability and rated at 0.25 A at 30 volts (AC or
DC).
Installation
The BG-12 pull station can be surface mounted to an SB-10 or SB-I/O surface backbox or
semi-ush mounted on a standard single-gang, double-gang or 4 (10.16 cm) square electrical
box. The optional BG-TR trim ring can be used if the BG-12 is to be semi-ush mounted.
Operation
To activate the dual-action pull station, push in and pull down on the handle. The word
ACTIVATED’ appears after the handle is pulled down. This will remain until the pull sta-
tion is reset.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O)
switch which closes upon activation of the pull station.
Resetting the Pull Station
1. To reset the BG-12 hex lock pull station, insert the supplied 9/64-inch hex wrench into
the lock until rmly seated and turn counterclockwise 1/4-turn.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
NOTE: Closing the door automatically resets the switch to the ‘Normal’ position. Open-
ing the door will not activate or deactivate the alarm switch.
STRIP GAUGE
1 2 3 4
IDC –
FROM
FACP +
TO NEXT
DEVICE
– IDC
+
WARNING: DO NOT LOOP WIRING
UNDER ANY TERMINALS. BREAK WIRE
RUN TO MAINTAIN IDC SUPERVISION.
P0205-00
Wiring
CAUTION! Do not detach the door of the pull station during installation. The door of
the pull station cannot be reattached to the backplate after the backplate has already been
installed onto an electrical box.
CAUTION!
Install the FireLite BG-12 pull station in accordance with these instructions,
applicable NFPA standards, national and local Fire and Electrical codes and the requirements
of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be con-
ducted in accordance with the appropriate NFPA standards. Failure to follow these directions
may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for
devices that have been improperly installed, tested or maintained.
ADA Compliance
For ADA compliance, if the clear oor space only allows forward approach to an object, the
maximum forward reach height allowed is 48 inches (121.92 cm). If the clear oor space
allows parallel approach by a person in a wheelchair, the maximum side reach allowed is
54 inches (137.16 cm).
BG-12
Manual Pull Station
WARNING! Do not loop wiring under any
terminals. Break wire run to
maintain IDC supervision.
Document 50964-1 I56-2263-003
P0194-01
Question and Answer IconNeed help?

Do you have a question about the Fire-Lite Alarms BG-12 and is the answer not in the manual?

Fire-Lite Alarms BG-12 Specifications

General IconGeneral
BrandFire-Lite Alarms
ModelBG-12
CategorySmoke Alarm
LanguageEnglish

Summary

Product Description and Ratings

BG-12 Manual Pull Station Description

Details the BG-12 pull station's dual-action, hex-lock reset, ADA compliance, and molded instructions.

Electrical Ratings

Specifies the BG-12 pull station's switch contact is gold-plated and rated at 0.25 A at 30 volts.

Installation and Operation

Mounting and Installation

Explains surface and semi-flush mounting options for the BG-12 pull station, including backbox types.

Operating the Pull Station

Describes how to activate the dual-action pull station and the 'ACTIVATED' indicator.

Resetting the Pull Station

Provides step-by-step instructions for resetting the BG-12 pull station using a hex wrench.

Important Safety and Compliance Notes

Wiring Supervision Warning

Crucial warning to not loop wiring under terminals; break wire run for IDC supervision.

Door Installation Caution

Caution against detaching the pull station door during installation as it cannot be reattached.

Installation and Testing Compliance

Caution to install and test per instructions, NFPA, codes, and AHJ requirements.

ADA Accessibility Requirements

Specifies maximum forward and side reach heights for ADA compliance.