15586 Rev E 5/14/93 P/N 15586:E 21
4.6 Trouble Test
Momentarily open the following circuits, one at a time, and check for a trouble signal:
Indicating Appliance Circuits 1 and 2
All initiating zones
Supervisory circuit
Municipal Box (if employed)
With fully charged battery, remove AC power and repeat the test procedure outlined in Section 4.2. Measure
battery voltage while the indicating appliances are activated. Reapply AC power and reset the panel. Replace
any battery with terminal voltage less than 85% of rating.
At the conclusion of testing, return all switches to their normal (up) positions. Notify the fire department, central
station and facility personnel that the test is complete.
4.7 Battery Test
4.8 Test Completion