Instruction Manual
D104296X012
LCP200 Local Control Panel
August 2018
10
Figure 6. Wiring Diagram 1, HART LOOP-Powered Configuration, Point-to-Point
LOGIC SOLVER
(USER SUPPLIED)
NOTES:
1 OPTIONAL CABLING TO RESET, TRIP, AND TEST CONTACTS. SHOWN ABOVE IS CABLING TO
1 RESET CONTACT.
2 CONNECT EITHER NO-C OR NC-C TERMINALS OF RESET, TRIP AND TEST CONTACTS. SHOWN
1 ABOVE IS RESET NO-C TERMINALS.
3 USE METAL CONDUIT FOR CABLING BETWEEN DVC6200 SIS AND LCP200 AS EMI SHIELD.
4 THE DIGITAL INPUT DOES NOT NEED TO BE CONNECTED FOR THE LCP200 TO OPERATE.
LCP200
GG22618 SHEET 2
3
1
DVC6200 SIS
TERMINAL BOX
(8-20 mA)
DIGITAL IN
ANALOG OUT
2
24V
POWER
AUX LOOP
DVC6200 SIS
TALK
TEST TRIP
NOT
AVAILABLE
AUX LOOP
RESET
OUT
CAL
4