LCP200 Local Control Panel
August 2018
14
Setup
In order for the LCP200 to operate properly, it must be connected to a DVC6200 SIS with firmware revision 3 or later,
or a DVC6000 SIS device with firmware revision 7 or later. Once the physical connections are made, use the following
checklist to configure the LCP200. Refer to the DVC6200 SIS instruction manual (D103557X012
) or the DVC6000 SIS
instruction manual (D103230X012
) if additional setup information is needed.
D Using a 475 Field Communicator select Configure > Guided Setup > Device Setup. Follow the prompts on the Field
Communicator:
Enter Supply Pressure and Unit
Enter Actuator Make, Model, and Size
Enter Partial Stroke test Starting Point, Relay Type and Zero Power Condition [select the “instrument connected to
local control panel (LCP200)” option]
D Use Device Setup to configure the digital valve controller with the LCP200.
D Continue to set up the digital valve controller according the normal set up procedure.
D Remember to place the instrument back in service before disconnecting.
Note
An alternative method to configure the LCP200 is through Manual Setup. Using the Field Communicator, select Configure >
Manual Setup > Instrument > Terminal Box > Edit Auxiliary Terminal Action > SIS Local Control Panel. When this setting is downloaded
to the device, an information screen will pop up advising that some additional parameters will be configured. Select Yes.