- 4 -
INSTALLATION:
The installation of this heater for use with No.1, No.2, Diesel or Kerosene and
shall conform with local codes or, in the absence of codes, with the National Fuel
Gas Code ANSI Z223.1/NFPA 54. Installation of the unit shall be in accordance
with the regulations of the authorities having jurisdiction or the CSA Standard
B139.
CLEARANCE TO COMBUSTIBLES:
TOP FRONT SIDES REAR FLUE PIPE
3 ft 10 ft 3 ft 3 ft 3 ft
FUEL: This heater will operate with No.1, No.2, Diesel or Kerosene.
Note: No.1 Fuel Oil or Kerosene must be used for
temperatures less than –10º C (8º F).
ELECTRICAL: WARNING
Electrical Grounding Instructions
This appliance is equipped with a three-prong (grounding)
plug for your protection against shock hazard and should be
plugged directly into a properly grounded three-prong
receptacle.
115v supply must be available. Please note that the heater
requires 15 amps for proper operation. Ensure appropriate
gauge extension cord is used.
• 12/3 AWG at 50 Feet
• 10/3 AWG at 100 Feet
FLUE PIPE: Flue pipe connection must terminate with a vertical run at
least 2ft long.
The vent outlet on the heater is 6” diameter. Certified venting
must be used at all times. Vent cap should be installed in
situations where downdrafts occur. All venting must
correspond with the CSA B149 standard or in its absence,
local codes.