This menu is for setup combine unit in order the menu will appear:
PR No
Engineers Code - 4706
Notes
Default
Unit
-
Language
E=English I=Italian D=Deutsch F=French
N=Netherland
E
1
Topup Required Y/N
Y
TOP-UP MENU
2
Low Pressure Alarm
Dependent on sensor range data
0.5
Bar
3
Low Pressure Warning
Dependent on sensor range data
0.6
Bar
4
Differential
+/- of cold fill pressure
0.2
Bar
5
Fill Pressure
system pressure + 0.3 vent allowance
1
Bar
6
High Pressure Warning
set 0.4 below the safety valve on
installation
2.6
Bar
7
High Pressure Alarm
Set 0.3 below the safety valve on
installation
2.7
Bar
8
Flood Limit
10
minutes
9
Excessive Start Quantity
0
10
Excessive Start Time
8
hours
11
Pump Number
1
STANDARD OPTION
12
Pump Type
Pump Type C (current monitored
centrifugal pump)
C
Pump Type P (current monitored Piston
pump)
Pump Type R (Not Current Monitored,
larger pump/motor contactor etc)
13
Pump Current Min Level
0.2
mA
14
Current Sense
Y
15
Periodic Pulse
Y
16
Pressure Sensor Max
Pressure
10
Bar
17
Pressure Sensor Min
Voltage
1
Volts
18
Pressure Sensor Max
Voltage
6
Volts
19
Slave Unit
SPC Mode, high water switch activates
pumps
N
20
Additive Unit
Changes High Water Message if not in
(Slave/SPC mode)
N
21
Overrun
Pump Overrun after achieving set
pressure (or Slave/SPC command is
deactivated)
5
Seconds