SUBMONITOR CONNECT
Installation and Operation Manual

Table of Contents

Questions and Answers

  • J
    John GibbsAug 14, 2025
    What happens if there's an over current in Franklin Electric SUBMONITOR CONNECT MT2211?
    • J
      Jeremy JacksonAug 14, 2025
      The Franklin Electric Relays will trip if the measured current is greater than the trip point setting for a duration that exceeds the over current trip time setting.
  • C
    Cheyenne EvansAug 17, 2025
    What happens if Franklin Electric SUBMONITOR CONNECT MT2211 have over voltage?
    • S
      Stephanie GonzalezAug 17, 2025
      The Franklin Electric Relays will trip if the average of the 3 line-to-line voltages exceeds the nominal voltage setting by the over voltage percentage setting continuously for a time exceeding the over voltage trip time setting.
  • M
    Michael EstradaAug 21, 2025
    What happens if Franklin Electric Relays have under voltage?
    • J
      johnsonjessicaAug 21, 2025
      The Franklin Electric Relays will trip if the average of the 3 line-to-line voltages is lower than the nominal voltage setting by the under voltage percentage continuously for a time exceeding the under voltage trip time setting.
  • A
    Amy JacksonAug 25, 2025
    What happens if Franklin Electric Relays have over power?
    • R
      Ryan McguireAug 25, 2025
      The Franklin Electric Relays will trip if the measured kW is greater than the kW trip point setting continuously for a time that exceeds the over power trip time setting.
  • A
    Aaron BakerAug 27, 2025
    What happens if Franklin Electric SUBMONITOR CONNECT MT2211 Relays have under power?
    • B
      Billy MorrisAug 27, 2025
      The Franklin Electric Relays will trip if the measured kW is less than the kW trip point setting continuously for a time that exceeds the under power trip time setting.
  • J
    Jason CarrollAug 31, 2025
    What happens if Franklin Electric SUBMONITOR CONNECT MT2211 have voltage phase unbalanced?
    • I
      ibarraderekAug 31, 2025
      The Franklin Electric Relays will trip if any of the 3 measured line-to-line voltages deviates from the average line-to-line voltage by a value greater than or equal to the voltage phase unbalance trip percentage setting for a time exceeding the voltage phase unbalanced trip time setting.
  • J
    Jennifer ParsonsSep 3, 2025
    What happens if Franklin Electric SUBMONITOR CONNECT MT2211 have current phase unbalanced?
    • G
      gravesjonathanSep 3, 2025
      The Franklin Electric Relays will trip if any of the 3 measured phase currents deviates from the average current by a value greater than or equal to the trip percentage setting.
  • J
    Justin MillerSep 6, 2025
    What happens if Franklin Electric SUBMONITOR CONNECT MT2211 have voltage phase loss?
    • S
      Steven SinghSep 6, 2025
      The Franklin Electric Relays will trip if the L-G voltage of any phase is more than 40% lower than the average voltage.
  • L
    Linda RodriguezSep 9, 2025
    What does unexpected current flow mean in Franklin Electric Relays?
    • J
      Jonathan PhelpsSep 9, 2025
      The Franklin Electric Relays will alarm if the starter detects current flow above a threshold of 0.2 A while the starter is in the stopped state.

Summary

Safety Instructions

Hazard Messages

Describes the formatting of safety alerts like DANGER, WARNING, CAUTION, and NOTICE.

Installation and Setup

Electrical Installation and Wiring

Discusses wiring guidelines, branch protection, and electrical connection procedures.

Start-Up Programming and Configuration

Guides through initial setup, menu navigation, and entering basic parameters.

Operation

Protection Features

Details various motor protection mechanisms like overload, temperature, and insulation checks.

Communications

FE Connect Mobile App

Describes the mobile app for wireless configuration, control, and monitoring.

Maintenance

Troubleshooting and Fault History

Guides on diagnosing issues using self-diagnostics and accessing the fault log.

Franklin Electric SUBMONITOR CONNECT MT2211 Specifications

General IconGeneral
CategoryRelays
ManufacturerFranklin Electric
ModelSUBMONITOR CONNECT MT2211
Frequency50/60 Hz
Communication ProtocolModbus RTU
Housing MaterialPlastic

Related product manuals