franklinwater.com
SUBMONITOR CONNECT
Installation and Operation Manual

Table of Contents

Questions and Answers

  • K
    Kelly RamosAug 14, 2025
    What happens if there's an over current in Franklin Electric SUBMONITOR CONNECT Relays?
    • C
      ccolemanAug 14, 2025
      The Franklin Electric Relays will trip if the measured current is greater than the trip point setting for a duration that exceeds the over current trip time setting.
  • J
    josephburnsAug 17, 2025
    What happens if Franklin Electric Relays have over voltage?
    • B
      Barbara Smith MDAug 17, 2025
      The Franklin Electric Relays will trip if the average of the 3 line-to-line voltages exceeds the nominal voltage setting by the over voltage percentage setting continuously for a time exceeding the over voltage trip time setting.
  • M
    madamsAug 20, 2025
    What happens if Franklin Electric SUBMONITOR CONNECT have under voltage?
    • J
      Jennifer BishopAug 20, 2025
      The Franklin Electric Relays will trip if the average of the 3 line-to-line voltages is lower than the nominal voltage setting by the under voltage percentage continuously for a time exceeding the under voltage trip time setting.
  • T
    tjohnsonAug 25, 2025
    What happens if Franklin Electric SUBMONITOR CONNECT have over power?
    • P
      Pamela PaulAug 25, 2025
      The Franklin Electric Relays will trip if the measured kW is greater than the kW trip point setting continuously for a time that exceeds the over power trip time setting.
  • M
    Matthew VegaAug 27, 2025
    What happens if Franklin Electric SUBMONITOR CONNECT Relays have under power?
    • B
      brendariveraAug 28, 2025
      The Franklin Electric Relays will trip if the measured kW is less than the kW trip point setting continuously for a time that exceeds the under power trip time setting.
  • J
    Joshua PayneAug 30, 2025
    What happens if Franklin Electric SUBMONITOR CONNECT Relays have voltage phase unbalanced?
    • D
      david09Aug 31, 2025
      The Franklin Electric Relays will trip if any of the 3 measured line-to-line voltages deviates from the average line-to-line voltage by a value greater than or equal to the voltage phase unbalance trip percentage setting for a time exceeding the voltage phase unbalanced trip time setting.
  • R
    Richard BoydSep 3, 2025
    What happens if Franklin Electric SUBMONITOR CONNECT Relays have current phase unbalanced?
    • C
      Chelsey HurleySep 3, 2025
      The Franklin Electric Relays will trip if any of the 3 measured phase currents deviates from the average current by a value greater than or equal to the trip percentage setting.
  • T
    Timothy MooreSep 6, 2025
    What happens if Franklin Electric Relays have voltage phase loss?
    • E
      Eric AndersonSep 6, 2025
      The Franklin Electric Relays will trip if the L-G voltage of any phase is more than 40% lower than the average voltage.
  • M
    Mr. Brandon MoranSep 10, 2025
    What does unexpected current flow mean in Franklin Electric Relays?
    • J
      Jamie MarshallSep 10, 2025
      The Franklin Electric Relays will alarm if the starter detects current flow above a threshold of 0.2 A while the starter is in the stopped state.

Summary

Safety Instructions

Hazard Messages

Describes safety message formats and symbols used in the manual.

Installation and Setup

Electrical Installation

Details wiring guidelines and mounting procedures for electrical setup.

Start-Up Programming

Covers the initial configuration and setup process.

Enter Basic Parameters

Details the initial parameter settings required for operation.

Programming: Advanced Setup > Motor Protection > Current

Covers advanced settings for motor current protection.

Operation

Protection Features

Overviews the various motor protection functions.

Communications

FE Connect Mobile App

Introduces the mobile application for configuration and control.

Maintenance

Troubleshooting

Provides guidance on identifying and resolving issues.

Fault and Alarm Descriptions

Details the descriptions and default settings for various faults and alarms.

Franklin Electric SUBMONITOR CONNECT Series Specifications

General IconGeneral
BrandFranklin Electric
ModelSUBMONITOR CONNECT Series
CategoryRelays
LanguageEnglish