INSTALLATION AND SETUP
Programming: Advanced Setup > Motor Protection > Voltage
21
Programming: Advanced Setup > Motor Protection > Voltage
Ground Fault Menu
424 RW N Trip/Alarm 0 - Off
1 - Fault and Alarm (default)
2 - Alarm only
Choose the type of response for ground fault current pro-
tection.
425 RW N Current Level 1 A to A; default = 1.0 A Amount of ground fault current that will trigger a fault
condition.
No Current
426 RW N Trip/Alarm 0 - Off (default)
1 - Fault and Alarm
2 - Alarm only
Choose the type of response for no current detected
when current is expected.
Unexpected Current
427 RW N Trip/Alarm 0 - Off (default)
1 - Fault and Alarm
2 - Alarm only
Choose the type of response for when unexpected cur-
rent is detected.
Out of Calibration Menu
428 RW N Trip/Alarm 0 - Off
1 - Fault and Alarm (default)
2 - Alarm only
Choose the type of response when the measured peak
inrush current is outside of the range of 400% to 1400%
of the user-set FLA.
Max Start Time Menu
429 RW N Trip/Alarm 0 - Off (default)
1 - Fault and Alarm
2 - Alarm only
Choose the type of response for when the start time for
the motor is exceeded.
Mod
bus
RW RC
Menu / Parameter
Name
Range Description
Mod
bus
RW RC Display Name Range Description
Overvoltage Menu
432 RW N Trip/Alarm 0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Overvoltage Protection Enable
433 RW N Overvoltage Level 101 to 125; default = 110 Overvoltage Level Percentage
430
431
RW N Nominal Voltage 120.0 to 7,200.0;
default = 208.0 multi = 0.1
Nominal Voltage setting
434 RW N Time to Trip 1 to 120; default = 10 Overvoltage Delay Time in seconds
435 RW N Fault Reset Type 0 - Manual
1 - Automatic (default)
Overvoltage Reset Method
436 RW N Reset Retries 1 to 10; default = 3 When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
437 RW N Reset Delay 1 to 43,200; default = 900 The number of seconds between automatic resets.
Undervoltage Menu
438 RW N Trip/Alarm 0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Undervoltage Protection Enable
439 RW N Undervoltage
Level
75 to 99; default = 90 Undervoltage Level Percentage
430
431
RW N Nominal Voltage 120.0 to 7200;
default = 208.0 multi = 0.1
Nominal Voltage setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Franklin Electric SUBMONITOR CONNECT Series and is the answer not in the manual?

Franklin Electric SUBMONITOR CONNECT Series Specifications

General IconGeneral
BrandFranklin Electric
ModelSUBMONITOR CONNECT Series
CategoryRelays
LanguageEnglish

Related product manuals