INSTALLATION AND SETUP
Programming: Advanced Setup > Motor Protection > Voltage
21
Programming: Advanced Setup > Motor Protection > Voltage
Ground Fault Menu
424 RW N Trip/Alarm 0 - Off
1 - Fault and Alarm (default)
2 - Alarm only
Choose the type of response for ground fault current pro-
tection.
425 RW N Current Level 1 A to A; default = 1.0 A Amount of ground fault current that will trigger a fault
condition.
No Current
426 RW N Trip/Alarm 0 - Off (default)
1 - Fault and Alarm
2 - Alarm only
Choose the type of response for no current detected
when current is expected.
Unexpected Current
427 RW N Trip/Alarm 0 - Off (default)
1 - Fault and Alarm
2 - Alarm only
Choose the type of response for when unexpected cur-
rent is detected.
Out of Calibration Menu
428 RW N Trip/Alarm 0 - Off
1 - Fault and Alarm (default)
2 - Alarm only
Choose the type of response when the measured peak
inrush current is outside of the range of 400% to 1400%
of the user-set FLA.
Max Start Time Menu
429 RW N Trip/Alarm 0 - Off (default)
1 - Fault and Alarm
2 - Alarm only
Choose the type of response for when the start time for
the motor is exceeded.
Mod
bus
RW RC
Menu / Parameter
Name
Range Description
Mod
bus
RW RC Display Name Range Description
Overvoltage Menu
432 RW N Trip/Alarm 0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Overvoltage Protection Enable
433 RW N Overvoltage Level 101 to 125; default = 110 Overvoltage Level Percentage
430
431
RW N Nominal Voltage 120.0 to 7,200.0;
default = 208.0 multi = 0.1
Nominal Voltage setting
434 RW N Time to Trip 1 to 120; default = 10 Overvoltage Delay Time in seconds
435 RW N Fault Reset Type 0 - Manual
1 - Automatic (default)
Overvoltage Reset Method
436 RW N Reset Retries 1 to 10; default = 3 When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
437 RW N Reset Delay 1 to 43,200; default = 900 The number of seconds between automatic resets.
Undervoltage Menu
438 RW N Trip/Alarm 0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
Undervoltage Protection Enable
439 RW N Undervoltage
Level
75 to 99; default = 90 Undervoltage Level Percentage
430
431
RW N Nominal Voltage 120.0 to 7200;
default = 208.0 multi = 0.1
Nominal Voltage setting