Coolin
g
: 7,200 – 15,000 Btu
h
Heatin
g
: 6,400 – 13,300 Btuh (Heat Pump
)
8
,
500 – 17
,
000 Btuh (Electric Heat
)
Friedrich Models: PDE – Coolin
g
with or without electric heat
PDH – Heat Pum
p
with electric heat
All units shall be
f
actory assembled, piped, wired and
f
ully charged
with R-22. All units shall be certi
ed in accordance with ARI Standard
310 for air conditioners and ARI standard 380 for heat pumps. Units
shall be UL listed and carr
y
a UL label. All units shall be factor
y
run-tested to check operation and be manufactured b
y
Friedrich or
equiva
l
ent.
T
h
e
b
asic unit s
h
a
ll
not excee
d
16"
h
ig
h
x 42" wi
d
e. Overa
ll
d
ept
h
o
f the
u
nit fr
o
m the re
a
r
o
f the Frie
d
rich w
a
ll sleeve t
o
the fr
o
nt
o
f
the
d
ec
o
r
a
tive fr
o
nt c
o
ver sh
a
ll n
o
t excee
d
21
¼
"
.
The
u
nit sh
a
ll
b
e
d
esigne
d
so t
h
at room intrusion may
b
e as
l
itt
l
e as 7 ½". Insta
ll
ations
in walls deeper than 13 ¼" may be accomplished with the use o
f
a
wa
ll
s
l
eeve extension (PXWE). Unit s
h
a
ll
d
raw in am
b
ient air t
h
roug
h
both sides of an outdoor architectural louver or
g
rille measurin
g
42"
wide x 16" hi
g
h and shall exhaust air out middle portion of the louver.
T
h
e arc
h
itectura
l
l
ouver an
d
wa
ll
s
l
eeve s
h
a
ll
b
e
d
esigne
d
so t
h
at t
h
e
l
ouver may be installed
f
rom the inside o
f
the building.
R
EFRIGERATI
O
N
S
Y
S
TEM
The refrigeration s
y
stem shall be her-
meticall
y
sealed and consist of a rotar
y
compressor that is externall
y
mounte
d
on vi
b
ration iso
l
ators no sma
ll
er t
h
an 1 ¾"
d
ia. x 1 ½"
h
ig
h
;
condenser and evaporator coils constructed o
f
copper tubes and
aluminum plate
ns; and capillaries as expansion devices. Unit shall
have a fan slinger ring to increase effi cienc
y
and condensate disposal
and have a drain pan capable of retainin
g
1 ½
g
allons of condensate.
A tertiary condensate removal system shall also be incorporated
f
or
back up and shall over
ow through the wall sleeve and to the outside
of the buildin
g
as a safe
g
uard a
g
ainst dama
g
e to the interior room.
A
IR HANDLING
S
E
C
TI
O
N – The eva
p
orator and condenser fans
s
h
a
ll
b
e
d
irect
l
y
d
riven
b
y a sing
l
e, tota
ll
y enc
l
ose
d
,
b
a
ll
b
earing,
permanently lubricated split capacitor, “clam-shell" style
f
an
motor. Airflow shall be directed into the room by a single, injec-
tion molded, high-impact pol
y
st
y
rene discharge grille. The grille
shall have openin
g
s no lar
g
er than
3
/
8
"
hi
g
h x 3" wide to prevent
persona
l
injury or
d
amage to t
h
e PTAC unit, an
d
wi
ll
b
e reversi
bl
e
to a
ll
ow air to
b
e
d
irecte
d
upwar
d
or outwar
d
as
d
etermine
d
b
y
the inst
a
ller
.
The chassis shall have a built-in damper capable of providin
g
at least
60 CFM o
f
f
resh air into the conditioned area. A removable
ne mesh
screen shall
lter the incoming
f
resh air. There must be a provision
f
or lockin
g
the damper closed to ensure a proper seal
.
CO
NTR
O
L
S
– Covered controls shall be accessible in a com
p
artment
at least 9" wide with the controls no deeper than 1 ¼" in the openin
g
to
f
acilitate easy operation o
f
the unit.
The unit controls shall
f
eature an LED readout that can display either
room tem
p
erature or set
p
oint tem
p
erature. The unit shall receive
in
p
ut from the SMART CENTER
®
control panel throu
g
h push but-
tons
l
a
b
e
l
e
d
: ‘Coo
l
, ‘Heat’, ‘Hig
h
Fan’, ‘Low Fan,
,
’ an
d
‘Power’.
When 'O
', the unit may be put directly into cooling or heating
mode by pressing the ‘Cool’ or ‘Heat’ button.
The unit must have the
f
ollowing energy saving and convenience
f
eatures built-in:
Quiet start/stop fan dela
y
Room freeze
p
rotectio
n
Random com
p
ressor restar
t
Electronic temperature limitin
g
Wireless remote control read
y
Internal dia
g
nostic
s
The PTAC must also o er the abilit
y
to be controlled b
y
a remote
w
a
ll-m
ou
nte
d
therm
o
st
a
t with
ou
t
add
iti
o
n
a
l
a
ccess
o
ries
.
L
o
w v
o
lt-
a
g
e inputs will include: C (common), R (24V power), Y (coolin
g
), GL
(
fan low), GH (fan hi
g
h), W (heat) and B (reversin
g
valve on PDH heat
pumps onl
y
)
.
The PTAC unit must also be able to be controlled b
y
an optional hand
held wireless remote control. The remote control shall be ca
p
able
of all basic control functions of the PTAC includin
g
: power on/o ,
coolin
g
, heatin
g
, fan speed and temperature settin
g.
O
ther c
o
ntr
o
ls
a
ccessi
b
le with
ou
t rem
o
v
a
l
o
f the ch
a
ssis sh
a
ll incl
ud
e
f
an c
y
cle switch, fresh air vent control and emergenc
y
heat override
switch (heat pump onl
y
).
GENERAL
CO
N
S
TR
UC
TI
O
N – The w
a
ll sleeve sh
a
ll
b
e c
o
nstr
u
cte
d
of 18-gauge Galvanized zinc-coated steel. It shall be prepared b
y
a
p
rocess where it is zinc
p
hos
p
hate
p
retreated and sealed with a
chromate rinse, then powder coated with a pol
y
ester fi nish and oven
cured for durabilit
y
. The sleeve shall be shipped with a protective
weatherboard and a structural center su
pp
ort, and be insulated for
sound absorption and thermal effi cienc
y
. The grille or louver shall be
shipped separatel
y
and made from stamped or extruded anodized
aluminum. All louvers shall be in the horizontal
p
lane.
The front panel shall lock to the chassis b
y
means of two factor
y
-
supplied thumbscrews to prevent tamperin
g
. The front panel will
f
eature a contoured dischar
g
e with no sharp corners. The air fi lters
sh
a
ll
b
e re
u
s
ab
le
a
n
d
b
e
a
ccessi
b
le with
ou
t rem
o
v
a
l
o
f the fr
o
nt c
o
ver
.
The fi lters will feature an antimicrobial coatin
g
to prevent mold and
b
acterial
g
rowth.
All 265V units shall possess an integral, over-current time-dela
y
p
rotective device.
Diamonblue corrosion
p
rotection comes standard on all models.
Diamonblue protects the outdoor coil a
g
ainst deterioration, and
exten
d
s the life
o
f the
u
nit
.
The unit shall have a corrosion-resistant fan, fan shroud and drain
p
an
f
or corrosion protection and to prevent rust on the side of the buildin
g
b
el
o
w the
ou
t
doo
r l
ou
ver
.
WARRANTY – The warrant
y
is one
y
ear on all parts and 5
y
ears on the
sealed s
y
stem including compressor, indoor and outdoor coils and
refri
g
erant tubin
g.
HVAC Engineering Speci
cation
s
Digita
l
Pac
k
age
d
Termina
l
Air Con
d
itioners & Heat Pumps
Service co
d
e storage
Constant com
f
ort room monitoring
Instant
h
eat
h
eat pump mo
de
Des
k
contro
l
termina
l
s
Indoor coil
f
rost sensor
Auxiliary
f
an control

Other manuals for Friedrich PDE07K

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Friedrich PDE07K and is the answer not in the manual?

Friedrich PDE07K Specifications

General IconGeneral
BrandFriedrich
ModelPDE07K
CategoryAir Conditioner
LanguageEnglish

Related product manuals