71 FRIULINOX ALI GROUPS.R.L. A SOCIO UNICO
Via Treviso,4 - 33083 Taiedo di Chions (PN) -Italy
Service Manual
9.1.11. Defrost.Timeout: defrosting concluded by duration
see
par. 4.4,
7.2.1
par. 8.6.2
par. 8.6.4
par. 8.6.6
see
par. 9.2.6
Defrost.Timeout on display informs that defrosting has ended for duration,
parameter d3, and not for temperature, parameter d2
The alarm is recorded in the Service menu, under Alarms
The alarm can be caused by:
- incorrect set of the parameters that manage the defrost
- malfunction of the “E2” defrost heater
- “E8” evaporator bowl heater malfunction
- incorrect reading of the “NTC probe defrosting” evaporator probe which
compromises the correct defrosting end temperature d2 parameter
For more details, see paragraph "9.2.6Ice formation on evaporator"