Service Manual
9.2. Malfunctions not managed by board
9.2.1. The display board does not switch on
see
par. 10
see
par. 8.1
1. Check that there is power on the power socket where the equipment is connected
2. Access the electronic board and use the multimetre to check for power supply (230V)
at the board input (“faston” terminals L and N) see wiring diagram
If there is power supply and the board does not turn on, check for power supply (12VDC) at the T1 transformer output
If there is voltage (12VDC) and the board remains off replace the electronic board
If there is no voltage at “T1” transformer output (12VDC) replace the transformer