EasyManua.ls Logo

Fuji Electric RSG12KMTA - Outdoor Unit Specifications

Fuji Electric RSG12KMTA
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. Specifications
Type Inverter heat pump
Model name ROG07KMTA ROG09KMTA ROG12KMTA ROG14KMTA
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A 3.0 3.4 5.1 6.8
Fan
Airflow rate
Cooling
m
3
/h
1,650 1,650 1,700 1,680
Heating 1,450 1,450 1,470 1,580
Type × Q'ty Propeller fan × 1
Motor output W 23
Sound pressure level *1
Cooling
dB (A)
46 50
Heating 46 50
Sound power level
Cooling
dB (A)
61 65
Heating 61 62 65 66
Heat exchanger type
Dimensions
(H × W × D)
mm
504 × 650 × 18.2 504 × 630 × 36.4 504 × 881 × 36.4
Fin pitch 1.3
Rows × Stages 1 × 24 2 × 24
Pipe type Copper
Fin type
Type (Material) Corrugate (Aluminum)
Surface treatment Corrosion resistance
Compressor
Type × Q'ty Rotary × 1
Motor output W 550 900
Refrigerant
Type (Global warming potential) R32 (675)
Charge g 600 700 850
Refrigerant oil
Type RB74AF RB68A
Amount
cm
3
240 340
Enclosure
Material Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
mm
541 × 663 × 290 542 × 799 × 290
Gross 602 × 804 × 375 602 × 940 × 375
Weight
Net
kg
23 25 31
Gross 26 29 35
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 9.52 (Ø 3/8)
Method Flare
Pre-charge length
m
15
Max. length 20
Max. height difference 15
Operation range
Cooling
°C
-10 to 46
Heating -15 to 24
Drain hose
Material PP+LLDPE
Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.8 (O. D.)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 5 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.
*1: Sound pressure level
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
DESIGN & TECHNICAL MANUAL
- 40 -
OUTDOOR UNIT
ROG07-14KMTA

Table of Contents