3. Installation space
3-1. Models: ROG07KMTA, ROG09KMTA, ROG12KMTA, and
ROG14KMTA
¢
Space requirement
Provide sufficient installation space for product safety.
CAUTION
Keep the space shown in the installation examples.
If the installation is not performed accordingly, it could cause a short circuit and result in a lack of
operating performance.
Single outdoor unit installation
When the upper space is open:
Unit: mm
Obstacles at rear only Obstacles at rear and sides
100 or more
250 or more
100 or more
100 or more
Obstacles at front Obstacles at front and rear
600 or more
600 or more
100 or more
When there is an obstruction in the upper space:
Unit: mm
Obstacles at rear and above Obstacles at rear, sides, and above
100 or more
Max. 200
600 or more
250 or more
100 or more
Max. 200
100 or more
600 or more