EasyManuals Logo

Fujitsu AB*18LBAJ Service Instruction

Fujitsu AB*18LBAJ
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #65 background imageLoading...
Page #65 background image
Trouble shooting 17
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 1 : Check connection of around the Compressor components
OKOK
Indicate or Display:
Check Point 2 : Replace Main PCB
Outdoor Unit Main PCB Circuit
Compressor rotor location cannot detect
(Permanent Stop)
1. Defective connection of electric components 2. Main PCB failure
If Check Point 1 do not improve the symptom, change Main PCB.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
While running the compressor, if the detected rotor location is out of
phase with actual rotor location more than 90 degrees,
the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
02-27
Refer to error code table.

Other manuals for Fujitsu AB*18LBAJ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AB*18LBAJ and is the answer not in the manual?

Fujitsu AB*18LBAJ Specifications

General IconGeneral
BrandFujitsu
ModelAB*18LBAJ
CategoryAir Conditioner
LanguageEnglish

Related product manuals