SERVICE PARTS INFORMATION 5
Check Point : AB*14/ 18/ 24LBAJ
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Read Wire
445 8%
346 8%
124 8%
80.0 8%
80.0 8%
Resistance value
(AC)
Thermal protector
Pr
VIOLET
BLUE
PINK
RED
BLACK
WHITE
140°C
at 20°C
Indoor Unit Fan Motor
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
02-54
AB*14LBAJ
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Read Wire
222 8%
175 8%
279 8%
63.5 8%
63.5 8%
Resistance value
at 20°C
AB*24LBAJ
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Read Wire
291 8%
204 8%
182 8%
78.5 8%
78.5 8%
Resistance value
at 20°C
AB*18LBAJ
Check Point : AR*9LUAB/ 12/ 14/ 18/ 22LUAD
(AC)
Thermal protector
Pr
VIOLET
BLUE
PINK
RED
BLACK
WHITE
150°C
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Read Wire
90.3 8%
152 8%
222 8%
42.9 8%
42.9 8%
Resistance value
at 20°C
AR*12/ 14/ 18/ 22LUAD
Red Pink
Pink Violet
Violet Blue
Red Black
White Red
Read Wire
367 8%
145 8%
160 8%
62.6 8%
62.6 8%
Resistance value
at 20°C
AR*9LUAB