EasyManua.ls Logo

Fujitsu ABYG30LRTE - 2-4. Selection of pipe heat insulating material

Fujitsu ABYG30LRTE
343 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Twin type
H1
H2
L1L3
L2
NOTE: Be certain to install indoor units in
the same room because the combi-
nations are for simultaneous opera-
tion. The lengths after branching
should be equal if possible.
Model name (Outdoor unit) AOYG72LRLA AOYG90LRLA
Model name (Indoor unit) 36 kBtu/h × 2 45 kBtu/h × 2
Main pipe diameter
(L1) (Standard)
Liquid
mm (in)
12.70 (1/2)
Gas 25.40 (1)
Branch pipe diameter
(L2, L3) (Standard)
Liquid
mm (in)
9.52 (3/8)
Gas 15.88 (5/8)
Maximum piping length
(L1 + L2 + L3)
m 100*
Minimum piping length
(L1 + L2 + L3)
m 5
Maximum branch piping length
(L2, L3)
m 20
Maximum difference between branch
lengths (L2 to L3)
m 8
Maximum height difference (H1) (Indoor
unit to outdoor unit)
m 30
Maximum height difference (H2) (Indoor
unit to outdoor unit)
m 0.5
*: For the standard pipe diameter
- 181 -
2-2. Piping limitation 2. Pipe design
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Other manuals for Fujitsu ABYG30LRTE

Related product manuals