Installation
Mounting of indoor unit
For mounting, refer to the installation manual provided with indoor unit.
When installing this product to existing indoor units, adjust the installation height of the indoor
units to height 260 to 265 mm as shown below.
Unit: mm
260 to 265
Metal hanging fastener
Ceiling
Indoor unit
Fresh air intake kit
Pre-installation preparations
Attach the duct flange provided with screws.
The Fresh air intake kit can be used an external air intake on just one side. Use included sealed
plate to apply for different eye holes.
Apply insulation 1 to the installed duct flange parts (Do not apply to sealed areas).
2
1
2
1
3
screw × 4
screw × 4
Insulation 3
Overlap with each other
Insulation 3
Insulation 1
Insulation 1
Insulation 3
Paste start position
When pasting, make sure that there is no gap
between the insulation 2 (overlap is allowed)
250
+20
-0
mm
Cut the insulation 3 to
250
+20
-0
mm and then apply
When taking in the air in one side, paste the insulation in the order as shown below.
2
1
2
3
screw × 4
screw × 4
Insulation 3
Insulation 3
Insulation 3
Insulation 1
Overlap with each other
- 308 -
10-3. Fresh air intake kit for cassette type (UTZ-VXRA) 10. Optional parts installation
SYSTEM
DESIGN
SYSTEM
DESIGN