Circuit diagram example
Indoor unit
control PCB
*1
Example: Switch
Locally purchased
Connected unit
1
3
Signal
10 m*2
Connector
Contact capacity: DC 24 V or more, 10 mA or more.
*1: PCB of Communication kit is used for wall mounted
type .
*2: Make the distance from the PCB to the connected
unit within 10 m.
Use non-polar relays and switches.
Indoor unit type
1-pin 3-pin
(Polarity) (Polarity)
Compact cassette and Cassette - +
Slim duct and Duct - +
Floor/Ceiling - +
Ceiling - +
When function setting is "Operation/Stop" mode
Operation
Stop
On
Off
Input signal
Indoor unit
When function setting is "Forced stop" mode
Remote controller
On On On
Input signal
Indoor unit
Command
Remote control
operation invalidity
On
Off
Operation
Stop
Forced stop
Normal
Optional part
Indoor unit type Part name Model name
Compact cassette
External connect
kit
UTY-XWZX
Cassette UTY-XWZX
Slim duct UTD-ECS5A
Duct UTD-ECS5A
Floor/Ceiling UTY-XWZX
Ceiling UTY-XWZX
UTY-XWZX UTD-ECS5A