En-16
External input and external output6. 7.
Terminal position6. 7. 1.
Input 5
CN135
(ORANGE)
Outdoor unit PC board
CN131
(YELLOW)
CN136
(BLACK)
CN137
(BLUE)
CN134
(RED)
CN115
(BLACK)
CN133
(WHITE)
Input 4 Input 3 Input 1 Output 1
Output 2
CAUTION
Do not bundle the cable for base heater with other cables.
(Example)
In case of Outdoor unit
Insert the connector to CN134 (Red) and CN135 (Orange) of control PC board. (1)
Fix it to the wire with the attached cable tie.(2)
Clamp
CN134
(Red)
CN115
(Black)
Cable tie
(Accessory)
Wire
Do not clamp the base heater cable.
Clamp
CN135
(Orange)
External input terminal6. 7. 2.
Service parts: EXTERNAL INPUT WIRE A (9368777005)
Setting to low noise mode, outdoor unit operation peak control setting, emergency/
batch stop and electricity meter pulse are possible from the outside.
Except for wattmeter pulse reception (CN135) among external input terminals, only
the Master unit is effective.
Wiring method and speci cations
A twisted pair cable (0.33 mm*
2
(22AWG)) should be used. Maximum length of
cable is 150 m.
Use an external input and output cable with appropriate external dimension, de-*
pending on the number of cables to be installed
For each input, pin No.1 is of positive polarity and pin No.2 is of ground level.*
connected unit
connected unit
connected unit
connected unit
CN131
(Yellow)
CN133
(White)
CN134
(Red)
CN135
(Orange)
P. C .B
Input 1
Input 3
Input 4
Input 5
Operation behavior
Each input terminal works as follows.
Connector Input signal Status
Outdoor unit
Master Slave
Input 1
CN131 (Yellow)
OFF Normal operation
O
ON Low noise mode operation
Input 3
CN133 (White)
OFF Normal operation
O
ON
Outdoor unit operation peak
control
Input 4
CN134 (Red)
OFF Normal operation
O
ON
Batch stop or Emergency stop
operation *1, *2
Input 5
CN135 (Orange) *3
No pulse
No information from electricity
meter
OO
Pulse
Power usage information from
electricity meter
Slave unit can connect only input5 (CN135).
The operations of each input terminal and the selection of function are set with the
push button on the PC board of outdoor unit. About the setting, please refer to 7.4.
Push button setting.
Note :
*1: Batch stop or Emergency stop pattern can be selected by outdoor unit PC
board push button.
*2: The emergency stop function mounted in the V-II does not guarantee the
regulations of each country. For this reason, suf cient checking is necessary
regarding use.
Especially, since the fact that the equipment may not be emergency-stopped
in the case of breaking of the wiring to the external input terminals and com-
munication line, communication error due to noise, VRF external input circuit
trouble, etc. must be considered, the provision of double measures that add
direct interruption of the power supply by switch, etc. is recommended as a
precaution.
*3: Pulse input to CN135 must be width 50ms or more, and must be interval 50ms
or more.
External output terminal6. 7. 3.
Service parts : EXTERNAL INPUT WIRE A (9368777005)
You can detect the operation condition of outdoor unit and the abnormal situation
of both indoor and outdoor unit.
The external output terminal is only valid for Master Unit.
Wiring method and speci cations
Error status (Master unit only)
This output indicates the outdoor unit and connected indoor unit's "Normal" or "Error"
status.
Operation status (Master unit only)
This output indicates the outdoor unit's "Operation" status.
Connector Output voltage Status
CN136 (Black)
0 V Normal
DC 12 to 24 V Error
CN137 (Blue)
0 V Stop
DC 12 to 24 V Operation