En-19
24
High static pressure
mode
Standard
24
00
High static pressure 1
(equivalent to 0.12in.WG
(30Pa))
01
High static pressure 2
(equivalent to 0.32in.WG
(80Pa))
02
(Forbidden) 0 3
When installing a duct to the blow-off outlet of an outdoor unit, set the high static
pressure mode according to the static pressure of the duct to be installed.
Furthermore, use this setting if the air blow of an outdoor unit is poor, such as when
installed in a place with a low ceiling.
25
(Forbidden) 2 5 0 0
26
(Forbidden) 2 6 0 0
27
(Forbidden) 2 7 0 0
28
(Forbidden) 2 8 0 0
29
(Forbidden) 2 9 0 0
30
Energy saving
level setting *1
Level 1 (stop)
30
00
Level 2 (operated at 40%
capacity)
01
Level 3 (operated at 60%
capacity)
02
Level 4 (operated at 80%
capacity)
03
Level 5 (operated at 100%
capacity)
04
The capacity limit can be selected by the external input terminal (CN133) when
operating with the “Energy Saving Peak Cut function”.
The lower the level, the more the effect of energy saving, but the cooling/heating
performance will also drop.
32
(Forbidden) 3 2 0 0
33
(Forbidden) 3 3 0 0
40
Capacity priority
setting (in low
noise mode) *1
Off (quiet priority)
40
00
On (capacity priority) 0 1
If the cooling/heating performance becomes insuffi cient when the low noise mode is set,
it is possible to set “capacity priority” that automatically cancels the low noise mode (once
performance is restored, the mode will automatically return to the low noise mode).
41
Low noise mode
setting *1
Off (Normal)
41
00
On (Low noise mode) 0 1
42
Low noise mode
operation level
setting
*1
Level 1 (55 dB)
42
00
Level 2 (50 dB) 0 1
The noise level when operating in the low noise mode can be set.
60
Back up operation 1
*1
On
60
00
Off 0 1
61
(Forbidden) 6 1 0 0
62
(Forbidden) 6 2 0 0
63
(Forbidden) 6 3 0 0
70
Electricity meter
No. setting 1 *2
Setting number (x00)
70
00
Setting number (x01) 0 1
······ ··· ···
Setting number (x98) 9 8
Setting number (x99) 9 9
Set the ones digit and tens digit of the No. of the electricity meter connected to
CN135.
71
Electricity meter
No. setting 2 *2
Setting number (0xx)
71
00
Setting number (1xx) 0 1
Setting number (2xx) 0 2
Set the hundreds digit of the No. of the electricity meter connected to CN135.
72
Electricity meter
pulse setting 1 *3
Setting number (xx00)
72
00
Setting number (xx01) 0 1
······ ··· ···
Setting number (xx98) 9 8
Setting number (xx99) 9 9
Set the ones digit and tens digit of the No. of the electricity meter pulse setting
connected to CN135.
73
Electricity meter
pulse setting 2 *3
Setting number (00xx)
73
00
Setting number (01xx) 0 1
······ ··· ···
Setting number (98xx) 9 8
Setting number (99xx) 9 9
Set the hundreds digit and thousands digit of the electricity meter pulse setting
connected to CN135.
*1: Do not set this for outdoor units with Slave setting.
*2: When electricity meter No. is set to “000” and “201 to 299”, the pulses input to
CN135 become ineffective. Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to “0000”, the pulses input to
CN135 become ineffective. Available setting number is "0001" to "9999"
(1) Turn on the power of the outdoor unit and enter standby mode.
When system is normal•
POWER/MODE lamp lights up. (ERROR lamp is off.)
POWER/MODE lamp:
ON
ERROR lamp: OFF
SELECT button
ENTER button
MODE/EXIT button
POWER
LED105 LED104
ERROR
MODE
LED101
(GREEN)
MODE
/EXIT
SELECT ENTER
SW107
SW108 SW109
LED102
(RED)
7 segment LED indicator:
OFF
When system is abnormal•
Check the settings as there is an error in the settings for outdoor unit address (DIP switch
SET3-1, 2) or number of connected slave units (DIP switch SET3-3, 4).
POWER/MODE lamp:
ON
7 segment LED indicator:
"-" display
ERROR lamp:
Blinking
POWER
LED105 LED104
ERROR
MODE
LED101
(GREEN)
MODE
/EXIT
SELECT ENTER
SW107 SW108 SW109
LED102
(RED)
(2) Setting method
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons to confi gure settings accord-
ing to the procedures below.
(If no setting is made, the factory default setting will be displayed.)
: Press the “MODE/EXIT” button.
: Press the “SELECT” button.
: Press the “ENTER” button.
: Press the “ENTER” button for more than 3 seconds.
MODE/EXIT
SELECT
ENTER
ENTER
9378945111_IM.indb Sec1:199378945111_IM.indb Sec1:19 2012/11/14 09:49:062012/11/14 09:49:06