En-13
6.7. IR receiver unit (Optional parts)
For the installation method, please refer to the INSTALLATION MANUAL of IR receiver
unit.
Connection methods
• Connection terminals
Controller PCB
IR receiver unit
terminal (CN18)
• Wiring arrangement
Controller PCB
Clamps
Cable tie*
(locally purchased)
Core
6.6. Remote sensor (Optional parts)
For the installation method, please refer to the INSTALLATION MANUAL of remote
sensor.
Connection methods
• Connection terminals
Controller PCB
Remote sensor
terminal (CN8)
• Wiring arrangement
Controller PCB
Cable tie
(locally purchased)
Clamps
Remove the existing connector and replace it with the remote sensor connector (ensure
that the correct connector is used).
The original connector should be insulated to ensure that it does not come into contact
with other electrical circuitry.
Use conduit hole when external output cable is used.
Setting for room temperature correction
When a remote sensor is connected, set the function setting of indoor unit as indicated
below.
Function Number “30”:
Set the Setting Number to “00”. (Default)
Function Number “31”:
Set the Setting Number to “02”.
* Refer to “7.4. Function setting” for details about Function
Number and Setting Number.