En-15
(3) Remote controller address
i) 3-wire type
Rotary switch (RC AD SW)...Factory setting “0”
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from 0.
Setting Setting range Type of switch
Remote controller
address
0 to 15
Setting
example
0
RC AD
Example
If 4 indoor units are connected.
RC AD SW
0
RC AD SW
1
RC AD SW
2
RC AD SW
3
Indoor unit
Remote
controller
Indoor unit Indoor unit Indoor unit
RC AD SW 01234567
Address 01234567
RC AD SW 89ABCDEF
Address 8 9 10 11 12 13 14 15
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting “0”
Since the remote controller address settings are automatically confi gured, you do
not need to confi gure them.
If confi guring manually, it is necessary to confi gure both the indoor unit and the
remote controller.
For details, please refer to the remote controller manual.
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
A B C D
A B C D
Indoor
unit
Remote
controller
Confusion
Code change
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2 referring to the Table B.
DIP switch “SET3”
ON
OFF
SW
1
SW
2
SW
3
SW
4
Table B
Custom code
A (Factory setting) B C D
DIP switch SET3 SW1 OFF ON OFF ON
DIP switch SET3 SW2 OFF OFF ON ON
7.3. Static pressure mode
CAUTION
If the applicable static pressure does not match the static pressure mode, the static
pressure mode may be changed to another mode manually.
It is necessary to set up a static pressure mode for each usage of static pressure.
Static pressure can be set at site.
Relation between set values and static pressure are as the following table.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
Function Number Setting Number Setting Static Pressure
26
00 SP mode 00
01 SP mode 01
02 SP mode 02
03 SP mode 03
04 SP mode 04
05 SP mode 05
06 SP mode 06
07 SP mode 07
08 SP mode 08
09 SP mode 09
10 SP mode 10
11 SP mode 11
12 SP mode 12
13 SP mode 13
14 SP mode 14
31 Normal SP (Factory setting)
* Please refer to FAN PERFORMANCE CURVE within Design & Technical Data for the
features of each setting.
* If the Setting Number in AR45 is confi gured to "12 to 14", the operation is the same as
that in "11(SP mode 11)".
* If the Setting Number in AR36 is confi gured to "13 to 14", the operation is the same as
that in "12 (SP mode 12)".
* If the Setting Number is confi gured to be “31” Normal SP (factory setting), the static
pressure is 40Pa(AR24), 50Pa(AR30,AR36), and 60Pa(AR45).