6. FIELD SETTING
There are 3 methods for address setting by FIELD SETTING as follows.
Please set by either of the methods.
Each setting method is described in below (1) to (3).
(1)
IU AD, REF AD SW settings:
This section (6.1. Setting the address)
(2) Remote controller settings: Refer to the wired or wireless remote controller manual
for detailed setting information. (Set IU AD, REF AD
SW to 0)
(3) Automatic address settings: Refer to the outdoor unit manual for detailed setting
information. (Set IU AD, REF AD SW to 0)
6.1. Setting the address
Manual address setting method
The indoor unit address and the refrigerant circuit address can also be set up through the
wireless remote controller
CAUTION
Be sure to turn OFF the power before performing the field setting.
• Position and detail of the switches
You need to remove
the front panel. Refer to
“8. FRONT PANEL RE-
MOVAL AND INSTAL-
LATION”.
SET3
×10 IU AD ×1 ×10 REF AD ×1
SET4
For refrigerant
circuit address
For indoor unit
address
• Please set it according to the following procedures when setting manually.
CAUTION
Use an insulated screwdriver to set the dip switches.
Be careful not to make mistakes for switch settings.
6.1.1 Indoor unit address
• Rotary switch (IU AD × 1)....Factory setting “0”
• Rotary switch (IU AD × 10)....Factory setting “0”
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD
SW as shown in the Table A
6.1.2 Refrigerant circuit address
• Rotary switch (REF AD × 1)....Factory setting “0”
• Rotary switch (REF AD × 10)....Factory setting “0”
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A for
each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
Setting Setting range Type of switch
Indoor unit
address
0 to 63
Setting
example 2
IU AD × 10 IU AD × 1
Refrigerant
circuit address
0 to 99
Setting
example 63
REF AD × 10 REF AD × 1
• If working in an environment where the wireless remote controller can be used, the ad-
dresses can also be set using the remote controller.
• If setting the addresses using the wireless remote controller, set the indoor unit address
and refrigerant circuit address to “00”.
(For information on setting using the wireless remote controller.)
Forced thermostat off function
[“Edge” input only]
Connector Input signal Command
Ch3 of CNA03 or CNA04
OFF ON Thermostat off
ON OFF Normal
5.6.2 External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25m).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
When indicator etc. are connected directly
Indicator 1
Indicator 2
Indicator 3
Indicator 4
connected unit
P.C.B
CNB
01
When connecting with unit equipped with a power supply
CNB
01
P.C.B
Connected
device 1
Connected
device 2
Connected
device 3
Connected
device 4
connected unit Relay (Locally purchased)
Operation behavior
* If function setting "60" is set to "00"
Connector Output voltage Status
CNB01
External output 1
Pins 1-2
0V Stop
DC 12 V Operation
External output 2
Pins 1-3
0V Normal
DC 12 V Error
External output 3
Pins 1-4
0V Indoor unit fan stop
DC 12 V Indoor unit fan operation
External output 4
Pins 1-5
0V External heater OFF
DC 12 V External heater ON
Indoor unit fan setting for external heater
Fan setting when turning ON output to the connected external heater can be set by
changing Dip switch on PC board.
Dip switch
[SET2 SW3]
Fan setting when
ON is output to the
external heater
Explanation
OFF
(Factory setting)
OFF
For the fan setting details, see the
Design & Technical Manual.
ON ON