En-12
• Refrigerant address example
(Example) ADDRESS : 30
OPERATION indicator
lamp (Green)
TIMER indicator lamp
(Orange)
FILTER indicator lamp
(Red)
9 sec
1 cycle 12 sec
ON
OFF
1.0s 1.0s 1.0s
1.0s 1.0s 1.0s 1.0s
0.5s
0.5s
0.5s 0.5s 0.5s 0.5s
ON
OFF
ON
OFF
OFF
• Setting details
Function number Item Setting number
01 Indoor unit address 00 to 63
02 Refrigeration address 00 to 99
For use with a remote controller, set all rotary switches to 0, and refer to “6.1. Setting the
address” for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name Indication pattern
OPERATION indicator lamp (Green)
Function number; tens place (0.5s ON/0.5s OFF)
TIMER indicator lamp (Orange) Function number; ones place (0.5s ON/0.5s OFF)
FILTER indicator lamp (Red) Setting number: (0 to 9) (0.5s ON/0.5s OFF)
(Example) Function : 31, Setting number : 2
OPERATION indicator
lamp (Green)
TIMER indicator lamp
(Orange)
FILTER indicator lamp
(Red)
11 sec
10 sec
9 sec
1 cycle 12 sec
ON
OFF
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s 0.5s 0.5s
ON
OFF
ON
OFF
7. FINISHING
CAUTION
After checking for gas leaks (refer to the Installation Manual of the outdoor unit), perform
this section.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do
so may cause water leaks.
7.1. Connection pipe, cable and drain hose
Insulate the drain hose, if necessary, to prevent it from freezing.
(1) Insulate between pipes.
• For (A) Rear, (B) Right and (C) Bottom piping, overlap the connection pipe heat insula-
tion and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no
gap.
• For (D) Left bottom piping, (E) Left piping, (F) Left rear piping, butt the connection pipe
heat insulation and indoor unit pipe heat insulation together and bind them with vinyl
tape so that there is no gap.
((A) Rear, (B) Right and (C) Bottom piping)
Indoor unit pipe
(heat insulation)
Overlap the insulation.
Connection pipe
(heat insulation)
Bind the pipes together so
that there is no gap.
Vinyl tape
Seal A is used when the diameter
of gas pipe is Ø12.70 or more.
Butt connection pipe (heat insulation) against
the indoor unit pipe (heat insulation) and wrap
with seal A so that there is no gap.
(For (D) Left bottom piping, (E) Left piping, (F) Left rear piping)
• Wrap the area which accommodates the
rear piping housing section with cloth tape.
Connection pipe Indoor unit pipe
Cloth tape (Accessories)
Wrap with cloth tape.
• Bind the connection cable with
vinyl tape.
• Bundle the piping and drain hose
together by wrapping them with
cloth tape over the range within
which they fit into the rear piping
housing section.
Connection cable
(Transmission and Remote controller cable)
Connection cable (Power supply cable)
Vinyl tape
Pipe
(2) Temporarily fasten the connection
cable along the connection pipe with
vinyl tape.
(3) Fasten the connection pipe to the
outside wall with a saddle, etc.
(4) Fill the gap between the outside wall
pipe hole and the pipe with sealer
so that rain water and wind cannot
blow in.
Pipe
Cloth tape
Drain hose
Wrap with cloth tape
(5) Fasten the drain
hose to the outside
wall, etc.
Saddle*
Pipe
Outside wall cap*
*Locally purchased
Wall
(Outdoors)
Sealer putty*
GOOD
Drain
hose
Saddle
Lifted up Wave End in water
PROHIBITED
8. FRONT PANEL REMOVAL AND INSTALLATION
8.1. Intake grille removal and installation
Intake grille removal Intake grille installation
Open the intake
grille. While gently
pressing the left and
right mounting shafts
of the intake grille
outward “a”, remove
the intake grille in
direction of the ar-
row “b”.
b
a
While holding the
grille horizontal, set
the left and right
mounting shafts into
the pillow blocks
at the top of the
panel “c”. To latch
each shaft properly,
insert the shaft until
it snaps.
c
Press 4 places on the intake grille to close it com-
pletely.
8.2. Front panel removal
(1) Remove intake grille
(Reference the intake grille
removal.)
(2) Remove 3 caps.
(3) Remove wire cover.
(4) Remove 7 screws.
Screws (Wire cover )
Screws ( 6 position )
Caps ( 3 position )
Wire cover
(5) The front panel is pulled to the
front, raising the upper surface, and
a front panel is removed.
Front panel
9373370499_IM.indb 129373370499_IM.indb 12 7/28/2020 10:26:22 AM7/28/2020 10:26:22 AM