EasyManua.ls Logo

Fujitsu Airstage ASUB24TLAV1 - Page 466

Fujitsu Airstage ASUB24TLAV1
978 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SPECIFICATIONS
z
Control unit
Power supply (V) DC 12
Current (A) 0.10
Power consumption (W) 1.2
Temperature [°F (°C)]
Operating 32 to 114 (046)
Packaged 14 to 140 (-1060)
Humidity (%) Packaged 095 (RH) No condensation
Dimensions [H × W × D] [in (mm)]
1-11/16 × 4-5/8 × 5-1/2
(43 × 117 × 140)
Weight [g (oz)] 7 (200)
Network
The electrical characteristics RS485
Maximum cable length (m) 250
z
Refrigerant pressure sensor
Power supply (V) DC 5
±
0.25
Current (mA) 10 or less
Pressure range (MPa) 0 to 5.0
Output voltage (V) DC 0.5 to 4.5
Accuracy (%FS) at 1013hPa, at 5V
Include thermal error
±
2.0
at -4 to 176 (-20 to 80°C)
Temperature [°F (°C)]
Ambient -22 to 176 (-3080)
Fluid -40 to 248 (-40120)
Airtight pressure (MPa) 5.5
Test pressure (MPa) 7.5
Burst pressure (MPa) 25 or more
z
Joint pipe
Applicable rifregrant R410A
Airtight proof (MPa)
The leakage rate shall be less than
1
10
-5
mmHgl/s.
Add mixgass (N
2
+R410A)
pressure to 4.15
Airtight pressure (MPa) 4.15
Proof pressure (MPa) 6.23
Burst pressure (MPa) 12.6
Dimensions of pipe
[L × D] [in (mm)]
2-12/16 × 1/4
(70 × Φ6.35)
- (05 - 103) -
CONTROL
SYSTEM
CONTROL
SYSTEM