3-4. NETWORK CONVERTOR FOR L
ON
W
ORKS
®
MODEL: UTY-VLGX
The convertor for connecting VRF network system to the BMS
system built by L
ON
W
ORKS
®
open network, for manage small to
medium sized BMS and VRF network system.
A maximum of 128 indoor units can be connected to one Network
Convertor for L
ON
W
ORKS
®
.
VRF system can be centrally controlled or monitored from BMS via
UTY-VLGX.
A maximum of 4 Network Convertor for L
ON
W
ORKS
®
can be connected to one BMS.
SYSTEM DIAGRAM
z
Proper system diagram
Network
convertor for
L
ON
W
ORKS
®
(UTY-VLGX)
Network
convertor for
L
ON
W
ORKS
®
(UTY-VLGX)
L
ON
W
ORKS
®
Network
General-purpose
building control computer
(L
ON
W
ORKS
®
device)
Maximum 128
indoor units
Maximum 100
outdoor units
Maximum 4 Network convertor
for L
ON
W
ORKS
®
(UTY-VLGX)
Maximum 100
outdoor units
Maximum 128
indoor units
VRF network system 1
VRF network system 2
VRF network
Lighting
facilities
Security
system
Ventilation
system
Automatic re
alarm interface