DIMENSIONS
Unit :
in (mm)
3-7/16 (86.7)
1-1/16
(27)
1/4 (7)
1/4
(7)
3-7/16 (86.7)
2-7/8 (72.7)
2-7/8 (72.7)
Bottom side
Upper side
SPECIFICATIONS
Max. connectable indoor unit number 16
Input Power (W) 0.6
Temperature: °F
(°C)
Operating 32 to 114 (0 to 46)
Packaged 14 to 140 (-10 to 60)
Humidity (%) Packaged
0 to 95 (RH);
No condensation
Dimensions [H × W × D]: in. (mm)
1-1/16 × 3-7/16 × 3-7/16
(27 × 86.7 × 86.7)
Weight: lbs. oz. (g) 4 (100)
WIRING SPECIFICATIONS
Use Size Cable type Remarks
Remote controller
cable (2-wire type)
16 to 22 AWG
(0.33 to 1.25 mm
2
)
Sheathed PVC
cable*
Non-polar 2 core, twisted pair
Maximum cable length: 1640 ft (500 m)
Remote controller
cable (3-wire type)
22 AWG
(0.33
mm
2
)
Sheathed PVC
cable*
Polar 3 core
Maximum cable length: 82 ft (25 m)
Thermostat wires
18 AWG
(0.82
mm
2
)
Sheathed PVC
cable*
Maximum cable length: 164 ft (50 m)
: Use shielded cable in accordance with local rules for remote contoller cable.
PACKING LIST
Name and shape Quantity Application
Installation manual 1 Use during installation.
Screw
(M4 × 16 mm)
2 For mounting the thermostat convertor
- (05 - 150) -