2-18. MODBUS
®
CONVERTOR FOR VRF
MODEL: UT Y-VMGX
SWITCH POSITION
Set MODBUS
®
convertor rotary switch SET1 and Dip switch SET2, SET4, SET5, SET6,
SET7.
MODBUS
®
CONVERTOR REMOTE CONTROLLER ADDRESS
SETTING (SET 1)
z
Example
Refrigerant
circuit
address
SW setting
SET1 (x10)
(10 digit)
SET1 (x1)
(1 digit)
01
0 1
15
1 5
Factory setting is "00"
*Setting range 00 - 15 (Arbitrary numbers can be set).
*When the Rotary switch is set to 16 or more, Modbus
®
convertor Remote Controller Address setting is 15.
*
The sum total of the Touch panel controller, Central remote controller, Network convertor for Group remote controller
,Network convertor for L
ON
W
ORKS
®
and Modbus
®
convertor is a maximum of 16.
*Address of the Touch panel controller, Central remote controller, Network convertor for Group remote controller,
Network convertor for L
ON
W
ORKS
®
and Modbus
®
convertor must not be same.
*Modbus
®
convertor is connectable a maximum of 9 in 1 VRF network system.
- (07 - 137) -