1-2-4. INDOOR UNIT EXTERNAL INPUT / OUTPUT FUNCTION
SUMMARY
INDOOR UNIT EXTERNAL INPUT FUNCTION
Item
Dry
contact/
Apply
voltage
Function Specications
EX T. IN1 E X T. IN2 Terminal
Signal
type
External power
supply
Wire
size /
length
Allowable
voltage
Allowable
current
Indoor unit
input
function
specication
Dry
contact
DC 12 [V]
-
CNA02
(PIN1-3)
Edge
- -
AWG22
Twist /
Max.
Cable
length
492 ft.
(150 m)
CNA02
(Ch1:PIN1-3)
(Ch2:PIN2-3)
Pulse *1
-
CNA04
(PIN1-2)
Edge
Apply
voltage
-
CNA01
(PIN1-2)
Edge
DC 12-24
[V]
10 [mA]
or less
CNA01
(Ch1:PIN1-2)
(Ch2:PIN1-3)
Pulse *1
-
CNA03
(PIN1-2)
Edge
*1 : Default setting is Edge signal, if you use pulse signal, must be set Dip SW2-2 to ON position.
INDOOR UNIT EXTERNAL OUTPUT FUNCTION
Item
Dry
contact /
Apply
voltage
Function Specications
Output 1 Output 2 Output 3 Output 4 Terminal
Terminal
output
voltage
Wire
size
Maximum
length of
cable
Indoor unit
output
function
specication
Dry
contact
- - -
CNB01
(PIN1-2)
DC 12 [V]
AWG22
Twist
82 ft.
(25 m)
-
- -
CNB01
(PIN1-3)
- -
-
CNB01
(PIN1-4)
- - -
*
CNB01
(PIN1-5)
1-2-5. OPTIONAL PARTS
Usage Name and shapes Q'ty Models
For output port
EXTERNAL
CONNECT KIT
1 UTY-X WZXZC
For control input port
(Apply voltage terminal)
EXTERNAL
CONNECT KIT
1 UT Y-XWZXZB
For control input port
(Dry contact terminal)
EXTERNAL
CONNECT KIT
1 UTY-XWZ X ZD
For forced thermostat off port
(Apply voltage terminal)
EXTERNAL
CONNECT KIT
1 UTY-XWZXZ7
For forced thermostat off port
(Dry contact terminal)
EXTERNAL
CONNECT KIT
1 UTY-XWZXZE