1-5. CENTRAL REMOTE CONTROLLER
External input External output Input select Connector External connect kit
(Optional parts)
Control input -
Dry contact CN6 (and CN7) UT Y-XWZXZ7
Apply voltage CN11 (and CN12) UT Y-XWZXZ8
- Operation status
- CN9 UTY-XWZXZA
- Error status
1-5-1. EXTERNAL INPUT
This function performs “Emergency stop” or “All On / All Off” by using the signal to be input externally at external
input terminals.
INPUT SELECT
There are 2 kinds of input method of External input terminal: “Dry contact” or “Apply voltage
contact.
z
Dry contact
When a power supply is unnecessary at the input device you want to connect, connect to CN6
and C N7.
*1
PCB
CN6
(White)
CN7
(Green)
Connected unit
*1 : Short circuit detection resistance (R
ON
) : ≤ 500 (ohm).
Open circuit detection resistance (R
OFF
) : ≥ 100 (kilo-ohm).
* A twisted pair cable(22AWG) should be used. Maximum length of cable is 82 ft. (25 m)
- (08 - 53) -