EasyManuals Logo

Fujitsu AO G12KATA Series Service Manual

Fujitsu AO G12KATA Series
471 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #251 background imageLoading...
Page #251 background image
2-19. E: 53. Drain pump error (Indoor unit)
Indicator Indoor unit
Operation indicator 5 time flash
Timer indicator 3 time flash
Economy indicator Continuous flash
Error code E: 53
Detective actuator
Indoor unit main PCB
When Float switch is ON for more than 3 minutes.
Float switch
Forecast of cause
Float switch failure
Shorted connector/wire failure
Main PCB failure
Drain pump failure
Hose clogging
Check point 1. Check float switch
• Check operation of float switch. (any blocking by dust, etc.)
• Remove float switch and check ON/OFF switching operation by using a meter.
-> If float switch is abnormal, replace it.
↓
Check point 2. Check connector and wire
Check loose contact of CN9 and shorted wire (pinched wire).
-> Replace float switch if the wire is abnormal
↓
Check point 3. Check drain hose
Check drain hose.
-> If there is hose clogging. Please clear the clog.
↓
Check point 4. Replace the main PCB
If check point 1 to 3 do not improve the symptom, replace the main PCB and execute the check
operation again.
↓
End
Attention
Wall mount type does not have a float switch. In this case, replace main PCB and set up the origi-
nal address.
2-19. E: 53. Drain pump error (Indoor unit)
- (03-35) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu AO G12KATA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G12KATA Series and is the answer not in the manual?

Fujitsu AO G12KATA Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G12KATA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals