2-20. E: 57. Damper (Open/Close) detection limit switch error
Indicator Indoor unit
Operation indicator 5 time flash
Timer indicator 7 time flash
Economy indicator Continuous flash
Error code E: 57
Detective actuator
Indoor unit main PCB • When limit switch were not able to detect the close
though the damper close.(Upper air flow)
• When limit switch were not able to detect the open
though the damper open.(Upper & Lower air flow)
Limit switch
Damper
Forecast of cause
Limit switch failure
Shorted connector/wire
Damper faulure
Controller PCB failure
Check point 1. Check limit switch
• Check operation of limit switch. (any blocking by dust, etc.)
• Remove limit switch and check ON/OFF switching operation by using a meter.
-> If limit switch is detective, replace it.
↓
Check point 2. Check connector (CN18)/wire
Check loose contact of CN18/shorted wire (pinched wire).
-> Replace limit switch if the wire is abnormal
↓
Check point 3. Check Damper
• Check the obstruction of damper movement.
• Check the damper movement.
-> Replace damper if the damper is abnormal
↓
Check point 4. Replace the main PCB
If Check Point 1 and 3 do not improve the symptom, replace the main PCB.
↓
End
2-20. E: 57. Damper (Open/Close) detection limit switch error - (03-36) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu AO G12KATA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G12KATA Series and is the answer not in the manual?

Fujitsu AO G12KATA Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G12KATA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals