2-13. E: 3A. Indoor unit communication circuit (wired remote
controller) error
Indicator Indoor unit
Operation indicator 3 time flash
Timer indicator 10 time flash
Economy indicator Continuous flash
Error code E: 3A
Detective actuator
Wired remote controller (2-wire)
Detect the communication error of microcomputer and
communication PCB.
Indoor unit controller PCB circuit
Forecast of cause
Communication PCB defective
Indoor unit main PCB defective
Check point 1. Check the connection of terminal
After turning off the power supply, check and correct the followings
Indoor unit - Check the connection the communication PCB and the main PCB
Check Point 2 : Replace the communication PCB
If the Check point 1 is ok, replace the communication PCB
Check Point 3 : Replace the main PCB
If condition is doesn’t change, replace the main PCB
End
2-13. E: 3A. Indoor unit communication circuit (wired remote controller) error - (03-26) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu AO G12KATA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G12KATA Series and is the answer not in the manual?

Fujitsu AO G12KATA Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G12KATA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals