EasyManuals Logo

Fujitsu AO G12KATA Series User Manual

Fujitsu AO G12KATA Series
403 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
Installation space requirement
1,000
or more
1,000
or more
1,800
or more
262
or more
Strong and durable ceiling
Obstruction
Floor
Unit: mm
Maximum height from floor to ceiling (Unit: mm)
07 and 09 models 12 or larger models
Standard 2,700
High ceiling 3,000
3-way direction setting:
100 or more*
Unit: mm
NOTES:
To set “3-direction”, optional Air outlet shutter plate (UTR-YDZB) must be installed, and the “out-
let-direction” need to be switched to “3-way” by remote controller.
*When installing the indoor unit, be careful about the maintenance space.
In 3-way outlet mode, changing of ceiling height setting by function setting 20 is prohibited.
(Ceiling height setting [function setting 20] is allowed to be changed only in 4-way outlet mode.)
2-1. Compact cassette type
- (01-15) - 2. Dimensions
GENERAL
INFORMATION
GENERAL
INFORMATION

Table of Contents

Other manuals for Fujitsu AO G12KATA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G12KATA Series and is the answer not in the manual?

Fujitsu AO G12KATA Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G12KATA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals