EasyManua.ls Logo

Fujitsu AO G12KATA Series - High Temperature and High Pressure Release Control

Fujitsu AO G12KATA Series
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-8. High temperature and high pressure release control
The compressor is controlled as follows.
¢ Models: AOYG09KATA, AOYG12KATA, AOYG14KATA,
AOYG18KATA, and AOYG22KATA
Cooling mode
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
DE
Zone A
Zone B
Zone C
Zone D
Zone E
AB:
61°C
BC: 60°C
CD: 59°C
DE: 54°C
Zone Operation
Zone A Compressor is stopped.
Zone B
The compressor frequency is decreased.
-30 rps/30 sec.
Zone C -5 rps/60 sec.
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
Heating mode
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
DE
Zone A
Zone B
Zone C
Zone D
Zone E
AB: 61°C
BC: 55°C
CD: 53°C
DE: 50°C
Zone Operation
Zone A Compressor is stopped.
Zone B
The compressor frequency is decreased.
-25 rps/120 sec.
Zone C -3 rps/60 sec.
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
8-8. High temperature and high pressure release control - (04-37) - 8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Related product manuals