¢ Wall mounted type (For KMTB, KMCC, and KMCE)
• Rotation number range of compressor
Unit: rps
Connected model name Minimum rotation number Maximum rotation number
AOHG14KBTA2 12 89
AOHG18KBTA2 8 94
• Limit of maximum speed based on outdoor temperature
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
E zone
F zone
10°C
0°C
12°C
2°C
Outdoor
temperature drops
Outdoor
temperature rises
Unit: rps
– Model: AOHG14KBTA2
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH MED LOW QUIET
ASHG07KMTB
ASHG07KMCC
ASHG07KMCE
A zone 89 50 38 18
B zone 89 50 38 18
C zone 50 38 34 18
D zone 38 34 30 18
E zone 38 34 30 18
F zone 38 34 30 18
ASHG09KMTB
A zone 89 50 38 14
ASHG12KMTB B zone 89 50 38 14
ASHG14KMTB C zone 50 38 34 14
ASHG12KMCC
ASHG09KMCC
D zone 38 34 30 14
ASHG14KMCC
ASHG09KMCE
E zone 38 34 30 14
ASHG12KMCE
ASHG14KMCE
F zone 38 34 30 14
1-1. Cooling operation - (04-8) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND