¢ Wall mounted type (For KETE)
• Rotation number range of compressor
Unit: rps
– Model: AOHG14KBTA2
Model name Outdoor temperature zone Operating rotation number
ASHG07KETE
ASHG07KETE-B
X zone 18
J zone 18
Y zone 0
ASHG09KETE
ASHG09KETE-B
X zone 14
ASHG12KETE
ASHG12KETE-B
J zone 14
ASHG14KETE
ASHG14KETE-B
Y zone 0
– Model: AOHG18KBTA2
Model name Outdoor temperature zone Operating rotation number
ASHG07KETE
ASHG07KETE-B
X zone 14
J zone 14
Y zone 0
ASHG09KETE
ASHG09KETE-B
X zone 10
ASHG12KETE
ASHG12KETE-B
J zone 10
ASHG14KETE
ASHG14KETE-B
Y zone 0
• Compressor control based on room temperature
Ts+0.5°C
Ts -1.5°C
Ts-0.5°C
Ts+1.5°C
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts: Set temperature
1-3. Dry operation - (04-21) - 1. Rotation number control of compressor