Cooling operation
Switch the airflow AUTO, and indoor fan motor will run according to room temperature, as below.
On the other hand, if switched in HIGH—QUIET, indoor motor will run at a constant airflow of COOL
operation modes QUIET, LOW, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Cooling: Auto)
When room
temperature rises
When room
temperature drops
Tr - Ts ≥ 1.5°C
MED mode
LOW mode
LOW mode
1.5
°C > Tr - Ts ≥ 0.5°C
0.5°C > Tr - Ts
Tr - Ts ≥ 2.5°C
2.5
°C > Tr - Ts ≥ 1.5°C
1.5°C > Tr - Ts
Dry operation
During dry operation, fan speed setting can not be changed as shown in “Fan speed” above.
Heating operation
Switch the airflow AUTO, and the indoor fan motor will run according to a room temperature, as be-
low.
On the other hand, if switched in HIGH—QUIET, the indoor motor will run at a constant airflow of
HEAT operation modes QUIET, LOW, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Heating: Auto)
When the room
temperature rises
When the room
temperature drops
LOW mode
MED mode
HIGH mode
Tr - Ts ≥ -1°C
-2°C > Tr - Ts
Tr - Ts ≥ -1.5°C
-1.5°C > Tr - Ts ≥ -2.5°C
-2.5°C > Tr - Ts
-1°C > Tr - Ts ≥ -2°C
3-1. Indoor fan control - (04-29) - 3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Other manuals for Fujitsu AO G12KATA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G12KATA Series and is the answer not in the manual?

Fujitsu AO G12KATA Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G12KATA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals