Detective Actuators:
Wired remote controller ( 2-Wire )
Indoor unit Controller PCB circuit
Detective details:
When the address number set by auto setting and manual setting are
mixed in one RC group.
When the duplicated address number exists in one RC group.
Check Point 3 : Check Indoor unit controller PCB
Forecast of Cause :
1. Wrong wiring of RCgroup 2. Wrong remote address setting 3. Indoor unit controller PCB failure
4. Remote controller failure
Check Point 1 : Wire installation
Wrong wire connection in RCgroup (Please refer to the installation manual)
Change controller PCB and check the Error after setting remote controller address
Check if controller PCB damage
Check Point 2 : Wrong RCgroup setting
The given address number by auto setting (00) and the manual set number (Except 00)
were not existing in one RCG.
The remote controller address setting by U.I. were not existing same address.
The duplicated address number is not existing in one RCgroup
Trouble shooting 7
INDOOR UNIT Error Method:
Indoor unit address setting error
Indicate or Display:
Error code : 26
02-08
Outdoor unit : No indication
OK
OK

Other manuals for Fujitsu AO G18KATA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G18KATA Series and is the answer not in the manual?

Fujitsu AO G18KATA Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G18KATA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals