EasyManua.ls Logo

Fujitsu AO G30KATA Series - Page 11

Fujitsu AO G30KATA Series
81 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model name Outdoor temperature zone
Limitation of compressor
frequency
AOEG30KATA
AOEG36KATA
A zone 55 rps
B zone 52 rps
C zone 47 rps
D zone 39 rps
E zone 33 rps
F zone 25 rps
G zone 18 rps
H zone 20 rps
I zone 20 rps
J zone 21 rps
K zone 24 rps
AOEG45KATA
A zone 60 rps
B zone 57 rps
C zone 48 rps
D zone 36 rps
E zone 27 rps
F zone 24 rps
G zone 20 rps
H zone 20 rps
I zone 20 rps
J zone 26 rps
K zone 30 rps
1-5. Compressor frequency limitation by outdoor temperature - (01-8) - 1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Related product manuals