8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢ Model: AOHG36KBTB
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 8.0 A 7.5 A
50°C ≤ Ta < 52°C 12.0 A 11.5 A
42°C ≤ Ta < 50°C 14.0 A 13.5 A
2°C ≤ Ta < 42°C 18.0 A 17.5 A
Ta < 2°C 20.0 A 19.5 A
Heating
2°C ≤ Ta 18.0 A 17.5 A
Ta < 2°C 20.0 A 19.5 A
¢ Models: AOHG45KBTB and AOHG54KBTB
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 10.0 A 9.5 A
50°C ≤ Ta < 52°C 13.0 A 12.5 A
46°C ≤ Ta < 50°C 15.0 A 14.5 A
42°C ≤ Ta < 46°C 18.0 A 17.5 A
2°C ≤ Ta < 42°C 20.0 A 19.5 A
Ta < 2°C 24.0 A 23.5 A
Heating
2°C ≤ Ta 20.0 A 19.5 A
Ta < 2°C 24.0 A 23.5 A
8-4. Low pressure protection control (cooling mode)
After the compressor start-up and 10 minutes has passed
When the pressure sensor detected value is 0.68MPaG or less continues for 1minute, the com-
pressor frequency -8rps.
After the frequency of the compressor -8rps and 1 minute has passed
When the pressure sensor detected value is 0.68MPaG or less, continues for 1 minute, the com-
pressor continues frequency -8rps every 1 minute until the detected value becomes more than
0.68MPaG.
When the detected value becomes more than 0.78MPaG, this protection is released.
After the compressor start-up and 1 minute has passed
The detected value of pressure sensor is 0.02MPaG or less, continues for 5 minutes, the com-
pressor is stopped.
0.78MPaG
0.68MPaG
0.02MPaG
Release of protection
Hold
Compressor stop
-8rps every 1 minute
(When continues for 5 minutes)
8-3. Current release control
- (01-36) - 8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Other manuals for Fujitsu AO G36KBTB Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G36KBTB Series and is the answer not in the manual?

Fujitsu AO G36KBTB Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G36KBTB Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals