Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : ASU15RLQ
[Condition]
Ambient
empera
ur
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping 7.5m (Height difference 1m)
Power
voltage
60Hz - 230V
Operation
con
on
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
me
o
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatic
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
ASU15RLQ
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
ASU15RLQ
Measure the low pressure with the pressure meter at the service valve. Measure the
outdoor unit overall current with the current clamp meter at Power Cable.
length
08-02
[60Hz-230V]
3
3.5
4
4.5
15 20 25 30 35
In/outdoor ambient temparature
Outdoor total electric current [A]
RH50%
RH60%
RH70%
[C]
(95)([ F])(59) (68) (77) (86)
[60Hz-230V]
0.7
0.8
0.9
1
1.1
1.2
1.3
15 20 25 30 35
In/outdoor ambient temparature
High side puressure of
outdoor unit [Mpa]
RH50%
RH60%
RH70%
[C]
(95) ([ F])(59) (68) (77) (86)