EasyManua.ls Logo

Fujitsu AOU18RLXFZH - Page 56

Fujitsu AOU18RLXFZH
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Trouble shooting 19
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
86°F
12.6Resistance Value (k )
68°F
16.1
59°F-4°FTemperature(°F)
3.45Resistance Value (k )
122°F 140°F
5.18
104°FTemperature(°F)
Outdoor Thermistor Error
Outdoor Unit Main PCB Circuit
Outdoor Temperature Thermistor
When Outdoor Temperature Thermistor open or short-circuit is
detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or miss-wiring, reset the power.
Check Point2: Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
7.97
158°F
1.652.36
23°F14°F 32°F 41°F 50°F
115 62.3 46.6 35.2 26.9 20.7
OK
OK
Indicate or Display:
Outdoor Unit : LED 1 : 4 time Flash
Indoor Unit : Operation lamp: 7 time Flash, Timer lamp: 4 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 74]
Check Point3: Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-24
THERMISTOR
(DISCHARGE)
BROWN
BROWN
1
2
1
2
THERMISTOR
(COMPRESSOR)
1
2
BLUE
BLACK
BLACK
THERMISTOR
(HEAT SINK)
THERMISTOR
(OUTDOOR)
THERMISTOR
(PIPE)
1
2
1
2
CN25
CN26
CN23
CN22
CN21
BLACK
1
2
BLACK
THERMISTOR
(PIPE MID)
CN24
WHITE
GREEN
BLUE
RED
YELLOW

Other manuals for Fujitsu AOU18RLXFZH

Related product manuals