8-3. Current release control
The rotation number of compressor is controlled so that the outdoor unit input current does not ex-
ceeds current limit value set according to the outdoor temperature.
The rotation number of compressor returns according to the operation mode, when the current be-
comes lower than the release value.
¢ AOUH09LPAS1
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
122.0°F (50°C) ≤ Ta 3.5 A 3.0 A
114.8°F (46°C) ≤ Ta < 122.0°F (50°C) 3.5 A 3.0 A
104.0°F (40°C) ≤ Ta < 114.8°F (46°C) 4.0 A 3.5 A
53.6°F (12°C) ≤ Ta < 104.0°F (40°C) 5.5 A 5.0 A
35.6°F (2°C) ≤ Ta < 53.6°F (12°C) 5.5 A 5.0 A
Ta < 35.6°F (2°C) 5.5 A 5.0 A
Heating
62.6°F (17°C) ≤ Ta 5.5 A 5.0 A
53.6°F (12°C) ≤ Ta < 62.6°F (17°C) 6.0 A 5.5 A
41.0°F (5°C) ≤ Ta < 53.6°F (12°C) 7.0 A 6.5 A
Ta < 41.0°F (5°C) 7.0 A 6.5 A
¢ AOUH12LPAS1
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
122.0°F (50°C) ≤ Ta 3.5 A 3.0 A
114.8°F (46°C) ≤ Ta < 122.0°F (50°C) 3.5 A 3.0 A
104.0°F (40°C) ≤ Ta < 114.8°F (46°C) 4.0 A 3.5 A
53.6°F (12°C) ≤ Ta < 104.0°F (40°C) 6.0 A 5.5 A
35.6°F (2°C) ≤ Ta < 53.6°F (12°C) 6.0 A 5.5 A
Ta < 35.6°F (2°C) 6.0 A 5.5 A
Heating
62.6°F (17°C) ≤ Ta 5.5 A 5.0 A
53.6°F (12°C) ≤ Ta < 62.6°F (17°C) 6.0 A 5.5 A
41.0°F (5°C) ≤ Ta < 53.6°F (12°C) 7.0 A 6.5 A
Ta < 41.0°F (5°C) 7.0 A 6.5 A
8-4. Cooling pressure over-rise protection
When the outdoor unit heat exchanger temperature reaches trigger condition below, the compressor
is stopped and trouble display is performed.
Trigger condition 149.0°F (65°C)
8-5. Low outdoor temperature protection
When the outdoor temperature sensor detects lower than the trigger condition below, the compres-
sor is stopped.
Operation mode Cooling/Dry
Trigger condition 5°F (-15°C)
Release condition 14°F (-10°C)